50 hp soft starter, 37 kW three phase 240v, 400v, 480v, 690v AC motor starter for selection.
| Model | GS2-037 (220v, 240v), GS3-037 (380v, 400v, 415v), GS4-037 (460v, 480v), GS6-037 (575v, 690v). | ||
| Capacity | 50 hp (37 kw) | ||
| Current | 75 amps at 380v/480v, 150 amps at 220v | ||
| Weight | 5 kgs | ||
| Dimension | 270*146*160 mm | ||
| Input | Voltage | Three-phase 230v, 380v, 460v, 690v AC | |
| Frequency | 50Hz/ 60Hz | ||
| Adaptive Motor | Squirrel-cage three-phase asynchronous motor | ||
| Starting Times | It is recommended not to exceed 20 times per hour. | ||
| 485 Communication | DB9 interface, male plug, ① is RS485+, ⑥ is RS485- | ||
| Control Mode |
| ||
| Start Mode |
| ||
| Stop Mode |
| ||
| Protective Function |
| ||
| Ambient | Place to be used | Indoor location with good ventilation free from corrosive gas and conductive dust. | |
| Altitude | Below 1000M. It has to increase the soft starter rate power when the altitude is more than 1000M. | ||
| Temperature | -30 +55 oC | ||
| Humidity | 90%RH without dew condensation. | ||
| Vibration | <0.5G | ||
| Structure | Enclosure | IP 20 | |
| Cooling | Natural wind cooling. | ||
Details

Tips: Soft starter installation methods
- The soft starter should install indoors in accordance with the shell protection level (usually IP20) requirement.
- Should install vertically, in the top and bottom of the soft starter should leave space at least 200mm width to facilitate heat dissipation.
- If the control cabinet is equipped with thermal relay, should use segregation board to prevent cold or hot airflow blowing to the thermal relay, to avoid affecting the action value of the thermal relay.
- Carefully read the instructions to understand the function of each terminal, ensure correct wiring.
- Usually don't use megger test the phase and relative to the ground insulation resistance. If it is necessary, must let three-phase input and output short circuit, and unplug all the plugs on the control panel, and then testing.
- When the soft starter input connects to the power supply, the output will bring a high induction voltage when the load opens circuit or loss of phase. So when in installation, commission, maintenance and use, prohibit contacting the soft starter output terminal, so as not to causing electric shock accident.
- If soft starter connects compensation capacitors to improve the power factor, the capacitor must connect to the soft starter input terminal, not output terminal, otherwise it will cause damage to the soft starter.
- The soft starter input and output terminals can't be connected reversely, otherwise it may cause damage to the soft starter and motor.
- If the soft starter has bypass contactor, carefully wiring (connect the contactor main contact) , can't cause short-circuit accident.
- When measure the motor insulation resistance, must disconnect the three lines between soft starter before proceeding.
Product reviews
Control method of 50 hp soft starter
Jules
5/17/2021 1:21 AM
Can I start your 50hp soft starter remotely with a 120 volt switch?
Was this review helpful? (0/0)
50hp 480V soft starter
Oliver
11/6/2023 1:37 AM
We purchased a 50hp 480V soft starter last year and finally got around to installing it.
Upon start up it powered up and started the motor but would shut off after about 20-30 seconds.
We tried several different settings but could not get it to remain running
The application is a submersible motor and turbine pump.
The motor is 40Hp
Any help or guidance is appreciated
Upon start up it powered up and started the motor but would shut off after about 20-30 seconds.
We tried several different settings but could not get it to remain running
The application is a submersible motor and turbine pump.
The motor is 40Hp
Any help or guidance is appreciated
Was this review helpful? (0/0)
Use large-sized devices
Biente
1/12/2025 8:28 PM
I plan to use a greatly oversize unit to be certain that I can make the required number of reversals for one part of the application that could exceed your 20/hour limit. Since your unit is not fan cooled and the larger sizes are a tolerable price. If necessary, I could provide a little forced ventilation.
Was this review helpful? (0/0)
Only registered users can write reviews
Customers who bought this item also bought
7.5 hp (5.5 kW) VFD, 3 Phase 208V, 380V, 480V
GK3000-4T0055G
$415.08
7.5 hp (5.5 kW) VFD with wholesale price, 3 phase 208V/380V/480V 50Hz/60Hz for option, heavy duty variable frequency drive, 13 amps at 380V ~480V, strong overload capacity, manufacturer direct sale.
60 hp (45 kW) Soft starter, 90 A, 3ph 240v/400v/480v
GS-045
$543.91
Affordable 60 hp soft starter, 45 kW three phase 240v, 400v, 480v AC motor starter, protect AC induction motor from inrush current impact, buy from Chinese manufacturer directly.
30 hp (22 kW) Soft starter, 43 A, 3ph 240v/415v/480v
GS-022
$426.11
Low cost 30 hp soft starter, 22 kW 3 phase 240v, 415v, 480v affordable motor soft starter direct sale from manufacturer from China.
12 Amps 3 Pole AC Contactor 24V/110V/220V Coil
ATO-ACCON-012
$51.46
Buy AC contactors from manufacturer at good price, 3 pole contactor relay has the advantage of small volume, light wight and low cost. With coil voltages of 24V/110V or 220V AC, rated current 12A at 380V, 9A at 660V. As a bypass contactor frequently start and control AC electric motors.
10 hp (7.5 kW) VFD, Three Phase 220V, 440V, 480V
GK3000-4T0075G
$463.25
Affordable 10 hp (7.5 kW) VFD, three phase 220V/440V/480V input for option, three phase output variable frequency drive, 17 amps, V/F & vector control, manufacturer direct sale.