10 hp variable frequency drive, three phase 220V /440V /480V ±15%, IP20 enclosure.
Specification:
| Basics | Model | GK3000-4T0075G/ GK3000-2T0075G |
| Capacity | 10 hp (7.5 kW) | |
| Shipping weight | 5 kg | |
| Dimension | 272*172*182 mm for GK3000-4T0075G/ 330*200*200 for GK3000-2T0075G | |
| I/O Feature | Rated current | 17A at 380V ~ 480V, 32A at 220V ~ 240V |
| Input voltage | 3 phase 220V /440V /480V AC ±15% (Optional) | |
| Input frequency | 50Hz/ 60Hz | |
| Output voltage | 3 phase AC 0~input voltage | |
| Output frequency | 0Hz~1000Hz | |
| Over load capacity | 150% of rated current for 1 minute, 180% of rated current for 3 seconds | |
| Control Feature | Control mode | V/F control; Sensorless vector control; |
| Communication | RS485 | |
| Speed regulation | 1:100 | |
| Start torque | 150% of rating torque at 1 Hz | |
| Speed control accuracy | ≤±0.5% of rating synchronous speed | |
| Frequency precision | Digital setting: max frequency x± 0.01%; Analog setting: max frequency x± 0.2% | |
| Frequency resolution | Analog setting: 0.1% of max frequency; Digital setting: 0.01Hz | |
| Torque boost | Automatic torque boost, manual torque boost 0.1%~30.0% | |
| Interior PID controller | Be convenient to make closed-loop system | |
| Automatic energy save running | Optimize V/F curve automatically based on the load to realize power save running | |
| Automatic voltage regulation (AVR) | Can keep constant output voltage when power source voltage varies. | |
| Automatic current limiting | Limit running current automatically to avoid frequent over-current which will cause trip | |
| Environment | Enclosure rating | IP 20 |
| Temperature | –10℃~ +40℃; VFD will be derated if ambient temperature exceed 40℃; each rise 1℃, the derate will be 5% | |
| Humidity | 5%-95%, without condensation | |
| Altitude | ≤1000m; VFD will be derated if above 1000m | |
| Impingement and oscillation | Normal running:<5.9m/s2 (0.6g); Transportation:<15m/s2 (1.5g) | |
| Store environment | –20℃~ +60℃; no dust, no corrosive gas, no direct sunlight |
Note: ATO VFD Cannot be used as a power source, it Can only be directly connected to an induction motor to control the motor speed.
Tips: Variable frequency drive fault dynamic test method
The dynamic test can only be proceeding after the static test result is normal. Dynamic testing must note the following issues:
- Before powering, the input voltage must be confirmed. If connect 380V power supply into 220V VFD, the VFD will be burned.
- Check all the connections of the VFD to be correct connected and fastened. Improper connection may lead to failure, or seriously, to be burned.
- After power on, check the failure display content, and initially determine the reasons.
- If the fault is not displayed, first check whether the parameters are abnormal, and then reset the parameters, and start VFD to test U/V/W three-phase output voltage under no-load situation.
- When the output voltage is normal and three-phase equilibrium, start load test. And it's best to start full load test.
Product reviews
10 hp VFD related issues
Kunwoo
6/14/2021 9:13 PM
We are interested in acquiring a 10 hp VFD but I have many questions. Do you have resellers in mexico? The VFD has a industrial certification?
Was this review helpful? (0/0)
Suitable VFD recommended by ATO
Sandey
9/22/2021 8:10 PM
The pump is a 60Hz, 17.3 kw, 440 v, 31.7A submersible pump, three-phase motor.
What is the right 1 to 3-phase converter for this pump? Pumping water 267 m up to a tank from a water source.
What is the right 1 to 3-phase converter for this pump? Pumping water 267 m up to a tank from a water source.
Was this review helpful? (0/0)
Hi ATO
Noam
12/19/2022 9:57 PM
Hi, I have three phase motor, 7.5Hp, 11.8/20.4A, 380V, with 2800Rpm, is the GK3000-4T0075G will be good for the mission?
Was this review helpful? (0/0)
VFD parameter settings
carver
7/20/2023 12:43 AM
I have powered up the drive with the spindle motor wired into it.
Started the drive the spindle motor and drive will go to about 25hz.
And won’t change when I increase or decrease the desired hz.
Setting it runs for about 30 seconds and faults out with E-10.
Can you help me out with a list of parameter settings that I will need to run the spindle motor in a normal run mode from the controller panel?
Started the drive the spindle motor and drive will go to about 25hz.
And won’t change when I increase or decrease the desired hz.
Setting it runs for about 30 seconds and faults out with E-10.
Can you help me out with a list of parameter settings that I will need to run the spindle motor in a normal run mode from the controller panel?
Was this review helpful? (0/0)
Have any suggestions for VFD code?
doro
7/24/2023 2:02 AM
We are getting a random E-12 Error code on one of our VFDs
Model GK3000-4T0075G
The VFD is set for 14.9 RPM.
And is only drawing 3.7 -4.0 AMPS.
VFD is cool to the touch, not overheating.
Any suggestions?
Model GK3000-4T0075G
The VFD is set for 14.9 RPM.
And is only drawing 3.7 -4.0 AMPS.
VFD is cool to the touch, not overheating.
Any suggestions?
Was this review helpful? (0/0)
VFD acceleration and deceleration setting
beck
8/29/2023 12:10 AM
P0.12 and P0.13 are acceleration time and deceleration time.
We need to speed increase and decrease via terminals.
For example, please find the inverter we use in which terminals D13 and D14 allow for speed increase and decrease.
We will need to you if you have this option as I could find it in the manual you sent.
We need to speed increase and decrease via terminals.
For example, please find the inverter we use in which terminals D13 and D14 allow for speed increase and decrease.
We will need to you if you have this option as I could find it in the manual you sent.
Was this review helpful? (0/0)
Programming Complexity
Oalliope
11/23/2023 1:36 AM
While modern VFDs often come with user-friendly interfaces, programming the drive for specific applications may require a certain level of expertise. Adequate training or consultation with technical support may be necessary for users less familiar with VFD programming.
Was this review helpful? (0/0)
Affordable and Reliable GK3000-4T0075G
Nick
6/12/2024 10:12 AM
I have purchased six of these units over the past two years. They have held up great in the oil field where we run them on pump jacks. We have power issues in the field all the time like single phasing/ low voltage and lightning strikes and they almost always survive. Easy programming interface and fast technical support via email. About to buy two more!
Was this review helpful? (0/0)
I have a question
Masca
8/27/2024 12:08 AM
I have question about a 7.5kw VFD. How long does an auto tune normally take? I have tried it on a couple of drives and it seems to run fine but doesn't stop.
Was this review helpful? (0/0)
Buy a VFD
Pinole
3/12/2025 2:34 AM
We need to purchase a 10 Hp, 575V, 9.6 amps, 1770 RPM VFD. Can you provide it?
Was this review helpful? (0/0)
Only registered users can write reviews
Customers who bought this item also bought
7.5 hp (5.5 kW) VFD, 3 Phase 208V, 380V, 480V
GK3000-4T0055G
$415.08
7.5 hp (5.5 kW) VFD with wholesale price, 3 phase 208V/380V/480V 50Hz/60Hz for option, heavy duty variable frequency drive, 13 amps at 380V ~480V, strong overload capacity, manufacturer direct sale.
4.5 kW Air Cooled CNC Spindle Motor, 18000 rpm, ER32
ATO-SPINDLE-A4500
$705.88
Hot sale 4.5kW air cooled spindle motor for CNC router with high speed of 18000 rpm, ER32 collet, 2.27 Nm holding torque, works at 380V AC 300Hz, 4pcs P4 grade ceramic ball bearings which improves the service life under high speed revolution.
30A 277V/ 480V Locking Plug, 4 Pole 5 Wire
ATO-L22-30
$81.27
30A electrical locking plug with 4 pole and 5 wire, 277V and480V rated voltage. It is made of high quality nylon and full copper. The dielectric voltage withstand is 18000V minimum. Male plug and female plug for your choices.
5 hp (3.7 kW) VFD, 3 Phase 230V, 400V, 480V
GK3000-4T0037G
$293.51
Favorable price 5 hp (3.7 / 4 kW) VFD, three phase 230V, 400V, 480V, high performance vector variable frequency drive, IP20 enclosure, RS485 enabled, brand new direct sale by manufacturer.
15 hp (11 kW) VFD, 3 Phase 230V, 415V, 480V
GK3000-4T0110G
$634.44
Inexpensive 15 hp (11 kW) VFD, three phase 230V/415V/480V, high performance variable frequency drive, IP20 enclosure, RS485 enabled, brand new direct sale by manufacturer in China.