60 hp AC motor soft starter, 45 kW three phase 240v, 400v, 480v, 690v.
| Model | GS2-045 (220v, 240v), GS3-045 (380v, 400v, 415v), GS4-045 (460v, 480v), GS6-045 (575v, 690v). | ||
| Capacity | 60 hp (45 kw) | ||
| Current | 90 amps at 380v/480v, 180 amps at 220v, 55 amps at 690v | ||
| Weight | 5 kgs | ||
| Dimension | 270*146*160 mm | ||
| Input | Voltage | Three-phase 220v, 400v, 480v, 660v AC | |
| Frequency | 50Hz/ 60Hz | ||
| Adaptive Motor | Squirrel-cage three-phase asynchronous motor | ||
| Starting Times | It is recommended not to exceed 20 times per hour. | ||
| 485 Communication | DB9 interface, male plug, ① is RS485+, ⑥ is RS485- | ||
| Control Mode |
| ||
| Start Mode |
| ||
| Stop Mode |
| ||
| Protective Function |
| ||
| Ambient | Place to be used | Indoor location with good ventilation free from corrosive gas and conductive dust. | |
| Altitude | Below 1000M. It has to increase the soft starter rate power when the altitude is more than 1000M. | ||
| Temperature | -30 +55 oC | ||
| Humidity | 90%RH without dew condensation. | ||
| Vibration | <0.5G | ||
| Structure | Enclosure | IP 20 | |
| Cooling | Natural wind cooling. | ||
Details

Tips: The causes of soft starter SCR damage
1. When the motor starting, the overcurrent will breakdown the soft starter. It is recommended to check whether the power of soft starter matches the power of the motor and whether the motor is on-load starting.
2. The soft starter's cooling fan is damaged. It is recommended to replace the fan.
3. Start up frequently, and high temperature will damage SCR. It is recommended to control the number of times of starting.
4. The filter board is damaged, input default phase, it is recommended to replace the damaged components. There are many factors that cause this failure:
- Check whether the power incoming line and the motor incoming line are loose.
- Whether the output is connected with load, whether the load matches the motor.
- Using a multimeter to check whether the module or SCR of the soft starter is breakdown, and whether the trigger gate resistance meets the normal requirements (typically around 20-30 ohms).
- Whether the internal socket wiring is loose.
Customers who bought this item also bought
20 hp (15kW) VFD, 3 Phase 220V, 380V, 460V
GK3000-4T0150G
$697.14
Cheap price 20 hp (15 kW) VFD, three phase 220V, 380V, 460V variable frequency drive with good performance, IP20 enclosure, RS485 enabled, brand new direct sale by manufacturer.
20 hp (15 kW) Soft starter, 30 A, 3ph 220v/380v/480v
GS-015
$389.21
Cheap price 20 hp soft starter, 15 kW three phase 220v, 380v, 480v AC motor soft start, reduce motor starting current & voltage, protect motor from over-voltage, over-current and phase unbalance etc.
50 hp (37 kW) Soft starter, 75 A, 3ph 240v/400v/480v
GS-037
$479.12
Inexpensive 50 hp soft starter, 37 kW three phase 240v, 400v, 480v for selection, make induction motor in soft start & soft stop, sell by manufacturer directly.
75 hp (55 kW) Soft starter, 110 A, 3ph 220v/380v/480v
GS-055
$579.16
High quality 75 hp soft starter, 55 kW three phase 220v, 380v, 480v AC motor soft starter to protect motor from inrush current impact, buy it from manufacturer directly with wholesale price.
7.5 hp (5.5 kW) VFD, 3 Phase 208V, 380V, 480V
GK3000-4T0055G
$415.08
7.5 hp (5.5 kW) VFD with wholesale price, 3 phase 208V/380V/480V 50Hz/60Hz for option, heavy duty variable frequency drive, 13 amps at 380V ~480V, strong overload capacity, manufacturer direct sale.