5 hp VFD for sale online, with 1-phase 220V-240V input to 3-phase 380v output, 50Hz/ 60Hz input frequency, 9 amps rated current, 400V/ 415V output are available for selection.
Specification:
| Basics | Model | GK3000-CT0037 |
| Capacity | 5 hp (3.7 kW) | |
| Shipping weight | 5 kg | |
| Dimension | 247*159*179 mm | |
| Installation size | 148*235 mm | |
| I/O Feature | Rated current | 9 A |
| Input voltage | 1 phase 220~240V AC | |
| Input frequency | 50Hz/ 60Hz | |
| Output voltage (Optional) | 3 phase AC 380V/ 400V/ 415V/ 440V/ 460V (Note: 440V, 460V output voltage only for the 1-phase 240V input VFD) | |
| Output frequency | 0Hz~400Hz | |
| Over load capacity | 150% of rated current for 1 minute, 180% of rated current for 3 seconds | |
| Control Feature | Control mode | V/F control; Sensorless vector control; |
| Communication | RS485 | |
| Speed regulation | 1:100 | |
| Start torque | 150% of rating torque at 1 Hz | |
| Speed control accuracy | ≤±0.5% of rating synchronous speed | |
| Frequency precision | Digital setting: max frequency x± 0.01%; Analog setting: max frequency x± 0.2% | |
| Frequency resolution | Analog setting: 0.1% of max frequency; Digital setting: 0.01Hz | |
| Torque boost | Automatic torque boost, manual torque boost 0.1%~30.0% | |
| Interior PID controller | Be convenient to make closed-loop system | |
| Automatic energy save running | Optimize V/F curve automatically based on the load to realize power save running | |
| Automatic voltage regulation (AVR) | Can keep constant output voltage when power source voltage varies. | |
| Automatic current limiting | Limit running current automatically to avoid frequent over-current which will cause trip | |
| Environment | Enclosure rating | IP 20 |
| Temperature | –10℃~ +40℃; VFD will be derated if ambient temperature exceed 40℃; each rise 1℃, the derate will be 5% | |
| Humidity | 5%-95%, without condensation | |
| Altitude | ≤1000m; VFD will be derated if above 1000m | |
| Impingement and oscillation | Normal running:<5.9m/s2 (0.6g); Transportation:<15m/s2 (1.5g) | |
| Store environment | –20℃~ +60℃; no dust, no corrosive gas, no direct sunlight |
Note: ATO VFD Cannot be used as a power source, it Can only be directly connected to an induction motor to control the motor speed.
Tips: 5 hp 1-phase 220v to 3-phase 380v VFD benefits
- 5 hp single phase 220v to three phase 380v variable frequency drive can reduce the impact on the grid, it will not cause the problem of excessive peak-to-valley difference.
- VFD can accelerate the function controllable, so as to smoothly accelerate according to the needs of the user.
- The motor's and equipment stopping mode can be controlled by 1-phase to 3-phase VFD, so that the whole equipment and system is safer and the life span will be increased accordingly.
- Controlling the starting current of the motor, fully reducing the starting current and making the maintenance cost of the motor lower.
- Can reduce the wear and tear of mechanical transmission parts, thus reducing the purchase cost, and at the same time can improve the stability of the system.
- Reduces the motor starting current and provides more reliable variable voltage and frequency.
- Single phase 220v to three phase 380v VFD effectively reduce the reactive power loss and increase the active power of the grid.
- This 5 hp (3.7kW) VFD can optimize the process and can change quickly according to the process, also can realize the speed change by remote control PLC or other controllers.
Product reviews
VFD connection problem
Dfsloan
5/31/2021 12:01 AM
The motor I have is on an old wood shaper from the year 1941. The 3450 rpm motor is pulley to create 8500 at the working end of the cutting tool, I want to spin it to aprx 14,000 RPM, can I use your VFD?
Was this review helpful? (0/0)
Can I use VFD?
Janetb
9/26/2021 7:40 PM
I have 1-phase (L, N, G), 220V supply, and want to run split phase (L1, L2 G), 220V motor, so can I use GK3000-1S0004 drive?
Was this review helpful? (0/0)
I would like to use the existing safety switches and motor to control 5HP VFD
DeLisle
12/12/2022 7:13 PM
I would like to use the existing safety switches and motor to control 5HP VFD. Do the Rev and fwd terminals require closed circuit voltage continuously to operate, or does momentary cause it to run indefinitely? Can I use the P24 terminal to run through the existing motor controls to operate the Rev and fwd functions?
Was this review helpful? (0/0)
Suggestions about VFD voltage and output testing
Betty
2/28/2023 7:22 PM
How would you recommend testing the output on the VFD for the voltage and the frequency?
By changing the frequency or the voltage output with the parameters, we’re not able to see any changes at the output.
We don’t want to connect anything before making sure that we have the right measurements on the output.
We want to make sure of other things too, we’re trying to connect 220V single-phase/50 Hz to the VFD to have an output of 3-phases/50Hz.
The manual says that this model (GK3000-CS0037) is made for an input 220V 3-phases.
Also, the terminal showed in the manual doesn’t match the ones on the VFD.
I believe the one that we receive has been converted to match our needs since it came without a terminal screw on the “S” terminal (see picture). I need a confirmation of how should the 220V/50Hz single phase should be connected and how to verify the output.
By changing the frequency or the voltage output with the parameters, we’re not able to see any changes at the output.
We don’t want to connect anything before making sure that we have the right measurements on the output.
We want to make sure of other things too, we’re trying to connect 220V single-phase/50 Hz to the VFD to have an output of 3-phases/50Hz.
The manual says that this model (GK3000-CS0037) is made for an input 220V 3-phases.
Also, the terminal showed in the manual doesn’t match the ones on the VFD.
I believe the one that we receive has been converted to match our needs since it came without a terminal screw on the “S” terminal (see picture). I need a confirmation of how should the 220V/50Hz single phase should be connected and how to verify the output.
Was this review helpful? (0/0)
Is there any specific parameter specifications for that VFD?
kerri
2/28/2023 8:25 PM
Is the frequency suppose to be a stable 50Hz at the output? From the tests that we did, the frequency is showing higher or just fluctuating too much to have a good reading. We’ll continue testing with the instruction that you send us within the last email.
Let us know if there’s any specific parameter specifications for that model.
Let us know if there’s any specific parameter specifications for that model.
Was this review helpful? (0/0)
Settings that change on the VFD drive
gene
3/1/2023 8:07 PM
We connected the drive directly to the motor and started the system.
The motor starts up but only for few seconds. After that, the frequency dropped.
See below the video:
Télécharger la pièce jointe
Disponible jusqu’au 22 mars 2023
Can you please have a look and let us know if you see a settings that we should change on the drive.
See attached the changes already done.
The motor starts up but only for few seconds. After that, the frequency dropped.
See below the video:
Télécharger la pièce jointe
Disponible jusqu’au 22 mars 2023
Can you please have a look and let us know if you see a settings that we should change on the drive.
See attached the changes already done.
Was this review helpful? (0/0)
How to wire the VFD for external frequency control?
kalan
3/1/2023 11:00 PM
Another question, how do I wire up the VFD for external frequency control?
External potentiometer (spec)? How about external Up/Down frequency control?
What are connections and program the settings?
External potentiometer (spec)? How about external Up/Down frequency control?
What are connections and program the settings?
Was this review helpful? (0/0)
Is there a way to prevent an error from stopping the VFD?
Monzer
3/2/2023 8:42 PM
As requested, here is a video of the input voltage. The system error was an 07 (over voltage). Is there a way to prevent an error from stopping the VFD from operating when controlled by an external input? I will be 18 hours from this location, and if the VFD prevents the system from running, it will destroy a $200,000 area and 4 acres of new grass.
Was this review helpful? (0/0)
How should the function P3.46 be set with those 3 digits?
Shaun
3/6/2023 7:58 PM
Our plan is to put the function P3.46 = 1 (REV running mode) and to deactivate the Reverse with P0.04 = 10 (Running forward/Reverse prohibited). However, the function P3.46 on the VFD screen is showing a wider range of choice that is not mentioned on the manual. The screen is showing 3 digits. The first 2 digits go from 00 to 19 and the third one change only between 0 and 1. How should the function P3.46 be set with those 3 digits?
Was this review helpful? (0/0)
Above VFD suitable for open well submersible pump
Ramachandran
6/5/2023 1:33 AM
Can use this VFD for open well Submersible pump specification 3phase 380v, 50hz, 5hp, 2 pole, 3000rpm
Was this review helpful? (0/0)
Only registered users can write reviews
Customers who bought this item also bought
3 hp VFD, Single Phase to Three Phase VFD
GK3000-2S0022
$238.14
Low price 3hp VFD, convert 220V/230V/240V 1 phase to 3 phase, 9.6 amps, RS485 enabled, shipping weight 3kg, manufacturer direct sale.
3 hp VFD, 1-Phase 220V to 3-Phase 380V VFD
GK3000-CT0022
$446.92
1-phase 220V to 3-phase 380V VFD, 3 hp variable frequency drive for AC motor speed control at 50Hz/ 60Hz input frequency. 5.1 amps rated current, three phase 400V/ 415V AC output are customized.
7.5 hp VFD, 1-Phase 220V to 3-Phase 380V VFD
GK3000-CS0055G
$726.89
Customizable 7.5 hp (5.5 kW) single phase VFD, single phase 220V to three phase 380V variable frequency drive for AC motor speed control. Features 13 amps, RS485 communication interface, IP20 enclosure rating.
1 hp VFD, 1-Phase 220V to 3-Phase 380V VFD
GK3000-CS0007
$309.15
1 hp VFD for sale at cheap price, with 1-phase 220v input to 3-phase 380v output. 50Hz/ 60Hz input frequency, 2.1 amps rated current, RS485 enabled.
2 hp VFD, Single Phase to Three Phase VFD
GK3000-2S0015
$183.16
2 hp VFD, convert single phase to three phase for AC motor speed controls, 7 amps, IP20, RS485 enabled, manufacturer direct sale.