1 kVA static pure sine wave frequency converter (AC power supply) with built-in step up & step down transformer, 50Hz 60Hz up to 400Hz frequency conversion.
Specification:
| Model | HZ-60-1101 | |
| Capacity | 1 kVA | |
| Dimension | 420 (D)*330 (W)*180 (H) mm | |
| Weight | 45 kg | |
| Input | Voltage | 1 Phase 2 Wire: 110V, 120V, 220V, 230V, 240V ± 10% (Option *) |
| Frequency | 50 Hz, 60 Hz | |
| Output | Voltage, current | 120V Setting (Low grade): 0-150V, 8.4A |
| 240V Setting 0-300V (High grade): 0-300V, 4.2A | ||
| Load stabilization Rate | ≤±1% | |
| Frequency | 50Hz, 60Hz up to 400Hz adjustable Note: -When the output is 400Hz, the load capacity can only reach 50% of the rated capacity. -When the output is ≤120Hz, the load capacity can reach 100% of the rated value. -You can just adjust converter output frequency in the range (40-400Hz) for 400Hz option. | |
| Frequency Stability | ≤±0.01% | |
| Harmonic Distortion | Pure Sine Wave ≤2% | |
| Frequency meter | 4 digit, digital frequency meter, resolution 0.1Hz/Step | |
| Voltmeter | 4 digit, digital voltage meter, resolution 0.1V | |
| Ammeter | 4 digit, digital ammeter, resolution 0.1A | |
| Watt meter | 4 digit, digital Watt meter, resolution 0.1W | |
| Protection | With overload, short circuit, over temperature | |
| Instantaneous power failure protection and alarm device | ||
| Working Environment | Temperature | 0 - 40 deg.℃ |
| Humidity | 0 - 90% (Non condensation) | |
| Warranty | 18 months | |
Features and Safe Usage Guide
Here is a video that shows you the main features of ATO single phase frequency converter and how you can use it to effectively and safely power electric equipment.
Tips: Why does the aircraft use 400Hz power?
The frequency of AC power supply is usually 50Hz or 60Hz. Most of the countries in Asia and Europe adopt the electricity grid in the frequency of 50 Hertz. The United States, Japan, Canada, Taiwan in China, Brazil, the Philippines, Saudi Arabia and other countries adopt the electricity grid in the frequency of 60 Hz.
Then, why is the power source of the airplane 400Hz? Originally, if the frequency of the system is higher, fewer copper and steel materials will be used for the generator and transformer. Accordingly, the weight is lighter and the cost is lower. The shortcoming is that inductive reactance of the electrical device and circuit increases, the capacitive reactance decreases, the loss increases, and the transmission efficiency decreases. Conversely, the low frequency will increase the amount of materials used in electrical equipment, increase the weight and cost. Therefore, 50Hz and 60Hz are not suitable.
There is a well-known saying in the aviation industry: Struggle to decrease every gram! Therefore, the aviation motor is required to have a high frequency, so as to reduce the volume and decrease the weight. However, the electrical transmission line on the plane is not too long, thus the loss is not the main contradiction. Therefore, 400 Hz power supply is the choice.
What I mean is that if you set the output to 60Hz there is no other output on 400Hz? The reason I ask is that I am concerned about interference since we will locate the transformer in an equipment room. Is there any risk of interference from your equipment?
Ok, that was more than one question.
Input: 110v 60hz
Output: 220v 50hz
We are counting on your cooperation.
Today I configured the converter with the voltage set to 240V, frequency to 50Hz, and turned on the output for the UV lamp.
As with the last model, the frequency converter trips immediately without even trying to power the lamp.
There must be something restricting the output current, such as the “Current Limit Protection” you mentioned on 5/18/23 when troubleshooting our 500VA model.
This 1KVA model is rated for 8.4 Amps (low grade) and 4.2 Amps (high grade) current output…and our lamp specification states 1.6 Amps (has a 2.0 Amp fuse).
1. Why are these frequency converters unable to power this lamp?
2. Why does our old frequency converter have no problems, while the new models are unable to work?
HZ-60-1101
There is a com port as well, and I’m looking for software or document that could explain how to connect a computer to the power supply.
The equipment we are trying to supply is an Italian ""insta-freezer"" and it operates at 50Hz, 230V (line to neutral) and it draws 3.9 amps.
We replaced the fuse after it blew initially, and now every time we turn on the output switch, it trips the breaker in the house electrical panel (it does not blow the fuse).
Note: The breaker trips even when there is nothing plugged in to the output receptacle.
FYI the converter is supplied with a dedicated 240V (2-pole) 15A circuit. (2-hots and no neutral).
For your reference, I've attached a picture of the unit we are trying to supply power to.
Would you please lend me some assistance in trying to resolve this matter?