DC current sensor has measuring range of 400A/500A/1000A/2000A/3000A/5000A/8000A/10000A to 20000A.
Specification:
| Model | ATO-AHKC-KAA | ATO-AHKC-HBAA |
| Shipping weight | 1kg | |
| Hole size * | 64*16mm | 132*52mm |
| Measuring range of input current * | DC 0-400A ~ 0-2000A | DC 0-2000A ~ 0-20000A |
| Output signal | DC 4-20mA | |
| Zero offset current | ±0.05mA | |
| Offset current drift | ±0.04mA/℃ | |
| Linearity | ≤0.2%FS | |
| Power supply * | DC 24V±10% or DC 12V±10% | |
| Accuracy | 1.0%F.S. | |
| Response time | ≤1ms | |
| Withstand voltage | AC 2500V (between input, output and power supply) | |
| Work temperature | -25~+70℃ | |
| Storage temperature | -40~+85℃ | |
| Humidity | ≤95%RH (no dew formation, no corrosive gas) | |
| Elevation | ≤3500m | |
| Measuring method | Split-core type | |
| Installation | Screw fixation | |
400A to 20000A DC current sensor dimensional diagram:
| Model | Dimension (mm) | |||||
| W | H | D | a | e | N (Mounting) | |
| ATO-AHKC-KAA | 127 | 63 | 25 | 64 | 16 | 30 |
| ATO-AHKC-HBAA | 204 | 111.5 | 29 | 132 | 52 | 48*2 |
400A to 20000A DC current sensor wiring diagram:
Tips: 5 attentions for AC/DC current sensor
- The current sensor must properly select different measuring range based on the rated effective value of the current under test. The long time excess of the rated current will damage the last stage power amplifier tube (refer to the magnetic compensation current sensor). In general, the time of duration of double overload current must not exceed 1 minute.
- AC/DC current sensor with insulation voltage resistance of 3KV can work for a long time in 1KV and below AC systems and 1.5KV and below DC systems, current sensor with 6KV can work for a long time in the 2KV and below AC systems and 2.5KV and below DC systems, be careful not to use under overvoltage.
- When applying high-current DC system, it is worth noting for the core produces a larger residual magnetism which caused by the power supply open circuit or fault. Residual magnetism affects accuracy. The method of demagnetization is to connect an alternating current and gradually reduce the value of the original current without connecting a power supply.
- The current sensor's ability to resist external magnetic field is: The distance of two 2000A current sensors is 5~10cm, the current value is more than twice original current, the resulting magnetic field interference can be resisted. When the three-phase large current sensor is wiring, the interphase distance should be greater than 5~10cm.
- The primary coil temperature must not exceed 85 ℃, which is determined by the characteristics of ABS Engineering Plastics. High-temperature plastic for the shell can be customized.
Product reviews
Perfect DC current sensor
Dutton
8/23/2021 3:13 AM
For your DC current sensor, which panel meter would you suggest?
Was this review helpful? (0/0)
Allowable range of 2000A current sensor
Cate
10/8/2021 1:20 AM
For your current sensor of 2000A range, how much over-range is permitted before clipping. We are hoping for 2400A (120% )?
Was this review helpful? (0/0)
Sensor Sensitivity
Rosedale
10/27/2025 12:32 AM
If I purchase an ATO-CUS-DC20000 with a rated current of 0-2000A, what is its sensitivity when reading currents close to 100A?
Was this review helpful? (0/0)
Relevant Parameters
Kenny
2/23/2026 11:36 PM
The ATO-AHKC-KAA current sensor may detect 1200 amps under fault conditions, but the normal load is 120 amps. What is the accuracy of the output at 10% of the sensor's range (0-1200 amps)? A 0-600amp sensor would be more suitable, but what is the sensor's lifespan under a 1200amp fault condition?
Was this review helpful? (0/0)
Only registered users can write reviews
Customers who bought this item also bought
DC Current Sensor 50A/100A/200A/500A/1000A to 1500A
ATO-CUS-DC1500
$83.25
Hall effect DC current sensors are open loop current sensors, with split-core structure, 1ms fast response time, 1.0%FS accuracy, 4-20mA output signal, 12V/24V power supply, fixed installation, excellent linearity and strong anti-interference capacity. DC current sensors are widely used for DC current monitoring, system signal acquisition and feedback control.
Isolated DC Voltage Sensor 10mV to 1000V, Power Supply DC 12V/24V
ATO-VOS-DC1000
$141.96
DC voltage sensor uses modulation and demodulation technology to achieve input/output/power supply isolation. Isolated voltage transducer has measuring range from DC 10mV/50mV/75mV/5V/150V/300V/500V to 1000V, supply voltage DC 12V/24V, accuracy 0.2%FS, output signal 0-5V/0-10V/0-20mA/4-20mA and strong anti-interference capability. DC voltage sensor is widely used for voltage isolated measuring and control, such as electric power, remote monitoring, medical equipment, etc.
15V DC 10A 300W Switching Power Supply
ATO-SMPS-300-1015
$98.39
Factory price switching power supply transforms the full range of AC input to a stable DC voltage of 15V at the rated power 300W and rated current 10A, this high efficiency SMPS can be used for LED lights, printers, computers, monitoring cameras and industrial control.
Hall Effect Current Sensor 400A/2000A/3000A/5000A/8000A to 20000A
ATO-CUS-ACDC20000
$122.98
Hall effect current sensors are AC/DC universal current sensors, with non-invasive structure, 5us fast response time, 1.0%FS accuracy, 0-5V output signal, ±15V power supply, measuring range can be 0-400A ~ 0-20000A or even higher current. Open loop current sensors are widely used for AC and DC high current detection, such as the high frequency switching power supply and solar power supply management system.