20 kVA pure sine wave frequency converter, changing 230V 50Hz to 110V 60Hz, or 120V 60Hz to 240V 50Hz, voltage and frequency converter for Europe and US home appliances.
Specification:
| Model | HZ-50-1120 | |
| Capacity | 20 kVA | |
| Dimension | 680*500*970mm | |
| Weight | 180 kg | |
| Input | Voltage | 1 Phase 2 Wire: 110V, 120V, 220V, 230V, 240V ± 10% (Option *) |
| Frequency | 50 Hz, 60 Hz | |
| Output | Voltage, current | 110V Setting (Low grade): 0-150V, 166.4A |
| 220V Setting 0-300V (High grade): 0-300V, 83.2A | ||
| Load stabilization Rate | ≤±1% | |
| Frequency | 50Hz, 60Hz up to 400Hz adjustable Note: -When the output is 400Hz, the load capacity can only reach 50% of the rated capacity. -When the output is ≤120Hz, the load capacity can reach 100% of the rated value. -You can just adjust converter output frequency in the range (40-400Hz) for 400Hz option. | |
| Frequency Stability | ≤±0.01% | |
| Harmonic Distortion | Pure Sine Wave ≤2% | |
| Frequency meter | 4 digit, digital frequency meter, resolution 0.1Hz/Step | |
| Voltmeter | 4 digit, digital voltage meter, resolution 0.1V | |
| Ammeter | 4 digit, digital ammeter, resolution 0.1A | |
| Watt meter | 4 digit, digital Watt meter, resolution 0.1W | |
| Protection | With overload, short circuit, over temperature | |
| Instantaneous power failure protection and alarm device | ||
| Working Environment | Temperature | 0 - 40 deg.℃ |
| Humidity | 0 - 90% (Non condensation) | |
| Warranty | 18 months | |
Wiring and Testing a Single Cabinet Frequency Converter
Here is a video about the operating steps of the cabinet frequency converter. This video gives a rundown of how to wire and test a 1 single cabinet frequency converter using a multimeter.
Tips: Frequency (50Hz and 60Hz) interchange will affect AC contactor
The impedance of small-size contactor is very small. Under the premise of ignoring impedance voltage drop, the electromotive force is in direct proportion. When the frequency turns from 50Hz to 60Hz, the induced electromotive force increases to 1.2 times, so the corresponding control voltage shall be increased to 1.2 times. In order to satisfy the suction requirement, it is required to increase the control voltage. Otherwise, insufficient suction will result in the bounce and bad contact of the relay, thus eventually causing damage.
Do you supply it in Saudi Arabia, or do you have a local vendor here?
I am interested in a 60 to 50Hz frequency converter for 220V.
We have placed two RCS90 chiller units from TA instruments to support their DSC250. These chiller units are only available at 220 V / 6A / 50 Hz. While here at KAUST in the Kingdom, the only available is 220 V / 60 Hz.
For this, I am urgently looking for 1 or 2 suitable frequency converters that work at our 60 Hz cycle power. (50 Hz AC a DC a AC 60Hz).
Output: 2 Phase 400 V (L1-L2) 60 Hz.
We recently purchased a "20 kVA Single Phase Frequency Converter 60Hz to 50Hz" (http://www.gohz.com/20kva-frequency-converter).
I have finalized the installation of the frequency converter but once I connected my appliance to the converter, I had to realize that my optical communication was not woring anymore. When I power the appliance with our normal power supply (swiss power grid), I have no problems with the communication.
My current assumption is that the converter generates some kind of disturbance on the output, which disturbs the communication line. The communication board is a very high resistance circuit (10Mohm resistor) and I would think that this circuit somehow picks up some disturbances, or the disturbances are distributed via the appliance internal 5V power supply.
I have tried different kinds of filters at the output of the converter, but was not very succesfull in getting rid of the disturbances.
Is this an issue other customers had previously? Are there any possibilities to add some additional filters to the output of the converter?
I am looking forward to an answer and hopefully some recommendations on how to improve the quality of the output signal of the converter.
I figured that there are some interference. Do you have a recommendation of a suitable EMI / EMC filter?
Do you have an idea about the frequencies of these interference?
1. Our 235V 60Hz power is from a transformer output with an un-grounded delta configuration. Can we safely apply it to the HZ-50-1120 input?
2. We also have a 208V system which is grounded wye configuration. Can we safely apply it to the HZ-50-1120 input?
3. Can 120V (A to Neutral) be applied to the HZ-50-1120 input?
4. Is there any large capacitance in the input stage of HZ-50-1120 that can cause a high in-rush current?
Unfortunately, I run into another problem. I changed the input supply cord of the frequency converter. After changing the cord, I wanted to double-check if everything works. I turned the input AC breaker on the frequency convert, and after that, it immediately activated the fuse of my supply.
I was surprised by this, since everything worked before I changed the cable, and I am sure I connected all phases correctly. Now when I measure the resistance between neutral and phase 1 (Connectors R and N) the resistance only is 60 Ohm.
Since the resistance between R and N on the supply clamp is >1Mohm when I open the input circuit breaker, the low ohmic connection must be after the input breaker (inside the converter).
I double-checked if there was a problem with the cable I used, but the resistance of the cable is >1Mohm as well.
Do you have any idea, what could have gone wrong? If there was a short circuit current, what could possibly break inside the converter?
If you want any additional information do not hesitate to contact me.
I measured 407V~ for the line voltage (R-S, R-T, S-T) and 233V~ for the phase voltage (R-N, V-N, T-N), which is what I expected of our grid (swiss grid has 230V 50Hz. Phase voltage). Therefore I am sure the input wiring is correct.
What I fail to see at the moment is, how replacing the fuse could help me solve the problem of the low resistance connection between R and N when the input circuit breaker is ON. I measure 60ohm between R and N when the input circuit breaker is ON (measured without supply voltage on the converter).
Therefore when I turn the input circuit breaker ON while having the converter supplied, this leads to the fuse of my external power box being activated.
I fear that there is a defect in an internal component inside the converter, otherwise, I cannot explain the low resistance connection between R and N. I checked the internal fuse of the converter and it is still fine (0.2ohm). Are there any other checks I could perform to help identify the issue?
Is there a chance that the input start-up current is not always that high?
I managed to get the converter starting after rewiring the supply cord.
Anyway, I think the current situation is ok and we can continue with testing.
Thank you again for your support, I really appreciated your input.