Highly reliable 15 kVA solid state frequency converter, 220V/230V/240V 50 Hz input to 110V/120V 60 Hz output (vice versa), make international 50/60 Hz power system compatible easily.
Specification:
| Model | HZ-50-1115 | |
| Capacity | 15 kVA | |
| Dimension | 680 (D)*500 (W)*970 (H) mm | |
| Weight | 150 kg | |
| Input | Voltage | 1 Phase 2 Wire: 110V, 120V, 220V, 230V, 240V ± 10% (Option *) |
| Frequency | 50 Hz, 60 Hz | |
| Output | Voltage, current | 110V Setting (Low grade): 0-150V, 125A |
| 220V Setting 0-300V (High grade): 0-300V, 62.5A | ||
| Load stabilization Rate | ≤±1% | |
| Frequency | 50Hz, 60Hz up to 400Hz adjustable Note: -When the output is 400Hz, the load capacity can only reach 50% of the rated capacity. -When the output is ≤120Hz, the load capacity can reach 100% of the rated value. -You can just adjust converter output frequency in the range (40-400Hz) for 400Hz option. | |
| Frequency Stability | ≤±0.01% | |
| Harmonic Distortion | Pure Sine Wave ≤2% | |
| Frequency meter | 4 digit, digital frequency meter, resolution 0.1Hz/Step | |
| Voltmeter | 4 digit, digital voltage meter, resolution 0.1V | |
| Ammeter | 4 digit, digital ammeter, resolution 0.1A | |
| Watt meter | 4 digit, digital Watt meter, resolution 0.1W | |
| Protection | With overload, short circuit, over temperature | |
| Instantaneous power failure protection and alarm device | ||
| Working Environment | Temperature | 0 - 40 deg.℃ |
| Humidity | 0 - 90% (Non condensation) | |
| Warranty | 18 months | |
Wiring and Testing a Single Cabinet Frequency Converter
Here is a video about the operating steps of the cabinet frequency converter. This video gives a rundown of how to wire and test a 1 single cabinet frequency converter using a multimeter.
Tips: Influence of 50Hz 60Hz frequency exchange to rotating equipment
It mainly discusses the rotating body of the motor. For instance, when the 60Hz motor is connected with 50Hz power supply, under the premise of unchanged voltage, it can be known that the rpm reduces for 1.2 times when the frequency lowers for 1.2 times, the magnetic flux increases for 1.2 times, the no-load current increases. As the reactance value decreases, the starting current increases accordingly. If the voltage of the power supply is not reduced, the motor output torque will be increased. The temperature rise of the motor winding will rise. As a result, the motor might be damaged after being operated for a long period. Meanwhile, because of the breakage of the motor revolving speed, its air circulation decreases, resulting in the reduced ventilation quantity and weakened heat dispersion.
I want to purchase power supply specification mentioned below.
Input: 240vac
Output: 120vac, 60hz, 4amp.
Load: oxigen consentrater.
We need a converter that will be used in Africa and the power is 1000VA
Input: 110v 60Hz
Output: 220v 50Hz
Input: 50/60Hz
Input phase: Single
Output volt: 115VAC out-750VA; 26VAC OUT-500va total 750va
Output 400HZ(380 to 420 HZ adjust.
Phase single: What do you recommend?
2- the out put power required is (1ph-220v-50Hz)
3- the air condition capacity is 3 hp and the max current is 30 A
4- actually I'll use the output of the converter to operate the compressor only which the max current at startup will be 30A and the normal operate current will be 15A
Advise which converter model will be suitable? And I think the compressor inrush current will not be less than 90A, not 30A.
Full load of the machine does not exceed 3000W
The rated voltage is 220v
Rated frequency 50hz
Maximum current for smaller model 5A
Maximum current larger model 12A
It receives 60hz and then converts it to a higher Hz of 120?
I am in no way technically inclined and just took the thing because I thought I could use it in my house.