Thermocouple/RTD signal conditioner can input signal of K/B/S/E/PT100 and output signal of 0-20mA/4-20mA/0-5V/1-5V/1-10V/2-10V.
Specification:
| Model | ATO-SIGNI-1003S | |
| Weight | 130g | |
| Dimension | 117.5mm*110mm*13mm | |
| Input signal* | thermal resistance | Conventional: Pt100, Cu50 |
| thermocouple | K, E, S, B, J, T, R, N, WRe3-WRe25, WRe5-WRe26 | |
| mV signal | -120~120mV | |
| Output signal* | 0~20mA, 4~20mA, 0~5V, 1~5V, 0~10V, 2~10V | |
| Output load resistance | 4~20mA, 0~20mA: RL≤550Ω | |
| Transmission accuracy | See table below | |
| Isolation strength (between input/output/power) | 1500Vrms (1 min, no spark) | |
| Response time | ≤500ms (Single-channel) | |
| Temperature drift | ≤40ppm | |
| EMC | EMC conforms to GB/T18268 (IEC 61326-1) requirements for industrial equipment application | |
| Power supply | 20~35VDC | |
| Power consumption | Single-channel output: ≤1.0W | |
| Operating temperature | -20~60℃ | |
| Storage temperature | -20~60℃ | |
| Relative humidity | 25%~85% | |
| Installation method | 35mm DIN rail mounting | |
Transmission accuracy:
| Input signal type | Range | Accuracy | |
| TC | K/E/J/N/T | <300℃ | ±0.3℃ |
| ≥300℃ | ±0.1% F.S | ||
| S/B/R/WRe-series | <500℃ | ±0.5℃ | |
| ≥500℃ | ±0.1% F.S | ||
| RTD | Pt100/Cu100/Cu50 | <100℃ | ±0.1℃ |
| ≥100℃ | ±0.1% F.S | ||
Dimensional drawing (unit: mm):
Wiring diagram of Single-channel input and Single-channel output:

Wiring diagram of Single-channel input and Double-channel output:

Wiring diagram of Double-channel input and Double-channel output:

Product reviews
Easy Installation
Irabu
11/20/2024 2:02 AM
The signal conditioner is very easy to install. It provides a clear wiring diagram and is labeled with thermocouple and RTD sensor input ports, output ports, and power ports. The wiring can be completed quickly according to the instructions.
Was this review helpful? (0/0)
Only registered users can write reviews
Customers who bought this item also bought
Current Sensor AC/DC 0~1mA/10mA/50mA/0.5A/1A/5A
ATO-CUS-ACDC5
$126.37
Current sensors are AC/DC universal current sensors, with a low current measuring range from milliamp current 1mA to 5A. AC/DC current sensors adopt linear photoelectric isolation or modulation and demodulation principle, fast response, 0.5%FS high accuracy, good stability, small size, light weight, input current terminal connection, DIN rail installation. Isolated current sensors are widely used for AC sine wave current or DC bidirectional current measurement.
Isolated DC Voltage Sensor 10mV to 1000V, Power Supply DC 12V/24V
ATO-VOS-DC1000
$141.96
DC voltage sensor uses modulation and demodulation technology to achieve input/output/power supply isolation. Isolated voltage transducer has measuring range from DC 10mV/50mV/75mV/5V/150V/300V/500V to 1000V, supply voltage DC 12V/24V, accuracy 0.2%FS, output signal 0-5V/0-10V/0-20mA/4-20mA and strong anti-interference capability. DC voltage sensor is widely used for voltage isolated measuring and control, such as electric power, remote monitoring, medical equipment, etc.