Signal isolator with strong isolation can convert 4-20mA/0-20mA/0-5V/0-10V signal to standard signal or other customized signal.
Specification:
| Model | ATO-SINIR-502E |
| Shipping weight | 0.5kg |
| Dimension | 96*18*122mm |
| Structure | Pluggable PCB power board and separable isolating circuit module |
| Type of signal * | 4-20mA, 0-20mA, 0-5V, 0-10V |
| Power supply | DC 24V±10% |
| Accuracy | 0.1%FS |
| Number of input & output channels * | 1 input channel & 1 output channel, 1 input channel & 2 output channels, 2 input channels & 2 output channels |
| Stability | ≤0.2%/year |
| Output load | Current output: 0-350Ω, voltage output: ≥10kΩ |
| Power supply mode of input signal | Loop powered (switch up), external powered (switch down) |
| Installation | 35mm DIN rail |
Dimensional drawing:
Wiring terminal:
Tips: What is external powered signal isolator and loop powered signal isolator?
- External powered signal isolator
It need an independent DC 20-35V switching power supply. The signal isolator samples 4-wire current signal and outputs 4-wire current signal after isolation. The advantage of this approach is high accuracy of isolation transmission. Power, input and output are completely isolated. Multi channel system power supply does not need isolation, thus ensuring a high anti-interference performance. The input signal can be converted to other types of signal. - Loop powered signal isolator
In the actual industrial monitoring system, DCS, PLC or other display instruments adopt cards internal power supply, the cards have higher requirement on the signal isolation transmission accuracy, so does the distribution voltage of a 2-wire transmitter. However, the external powered isolator can't meet these conditions. Therefore, the loop powered isolator is selected. Such a signal isolator provides working power supply to the 2-wire transmitter and samples the 2-wire current signal output by the transmitter. It converts the 2-wire current signal to 4-wire current signal after isolation and then output. In this way, it not only retains the superior performance of the external powered signal isolator, but also meets the requirements of the output loop powered interface.
Product reviews
Signal isolator for VFDs
Diego
11/25/2018 7:53 PM
Signal isolator is specially used to manage all kinds of off-brand VFDs. As long as using the loop powered signal isolator, the VFD is not subject to any interference, and the working state is very stable.
Was this review helpful? (0/0)
Analog signal isolator is good for solving interference problem.
Ryan
1/25/2019 8:13 PM
The analog signal isolator is easy to use. I don't need to confirm whether to buy a loop powered isolator or external powered isolator, because it has both modes. I can use the switch to select the one I need. After measurement, the isolator accuracy is indeed very high and the stability is good. I'm so glad that the system's interference problem is solved. I hope to cooperate with you for a long time.
Was this review helpful? (0/0)
4-20mA signal isolator with high accuracy
Eric
2/22/2019 2:31 AM
We use the FLUKE725 process calibrator to calibrate ATO 4-20mA signal isolator. When the calibrator displays a standard output of 12 mA, fine adjusting potentiometer for calibration. After finishing the calibration, the accuracy of full range is better than 0.1%, and the linearity is better than 0.1%. It is great!
Was this review helpful? (0/0)
Analog signal isolator can be input both loop powered signal and external powered signal
Owen
7/25/2019 8:41 PM
The input signals of this analog signal isolator can be both loop powered signal and external powered signal. It's very powerful. In this case, I won't worry about buying a wrong one. And when installing in the site, it also saves the works of changing the lead wires and changing the PLC program. It's so great!
Was this review helpful? (0/0)
Only registered users can write reviews
Customers who bought this item also bought
Custom Order
ATO-CUSTOM
Pay for custom orders, or extra amount of existing orders.
Indicate the item specification you pay for, and specify PI / PO number if you have.
Indicate the item specification you pay for, and specify PI / PO number if you have.
Signal Isolator Input/Output K/B/S/E/PT100/0-20mA/0-10V
ATO-SIGNI-402E
$101.07
Signal isolator ATO-TS-TR/TS-TC series is a universal signal isolator that can be customized with various active and passive input signals, such as thermocouple K/B/S/E type, RTD Pt100 . The output signals can be 0-20mA. Signal isolator has pluggable terminals, 12.5mm thickness, high accuracy 0.1%FS.