The input, output, power supply and shell of the reactive power transducer are isolated from each other, which can prevent high-voltage signals from harming equipment and personnel. The compressive strength of the reactive power sensor is AC2Kvrms/min, and the insulation resistance is greater than 100 MΩ at DC 500V. It uses a 35mm standard rail or is fixed on a cabinet. The reactive power transducer has good quality and is easy to install.
Specification
| Model | ATO-PT-HDB-Q3 |
| Measurement | 3phase 3wire or 3phase 4wire (optional) |
| Input | AC Voltage: 57.7V, 100V, 220V, 380V, 450V, 600V, customization AC Current: 1A, 5A, 10A, 20A, customization (optional) |
| Standard Range | 0~173.2var, 0~866var, 0~3000var, 0~±173.2var, 0~±866var (optional) |
| Input Load | CT of voltage transformer: ≤0.1VA CT of current transformer: ≤0.2VA |
| Allow Overload | Voltage × 1.2 times the nominal value continuous Current × 1.2 times the nominal value continuous Current × 10 times the nominal value for 10s |
| Accuracy | 0.2, 0.5 (optional) |
| Response Time | ≤400ms |
| Output Channel | 1 channel, 2 channels, 3 channels, 4 channels (optional) |
| Output Voltage | 0-10V, 0-5V, 1-5V (load resistance = input voltage/10mAdc) |
| Output Current | 0-1mA, 0-10mA, 0-20mA, 4-20mA (Load resistance=10VDC/output current) |
| Other Output | RS485, customization |
| Output Ripple | ≤0.5% RO peak |
| Work Environment Temperature and Humidity | 0~50℃/less than 80% relative humidity (non-condensing state) |
| Storage Conditions Temperature and Humidity | -20~70℃/less than 70% relative humidity (non-condensing state) |
| Aux.power Supply | DC12V, DC24V, AC220V, DC220V, AC110V, DC110V, 2-wire circuit power supply (optional) |
| Isolation | Input/output/power supply/shell |
| Power Consumption | DC about 3W, AC about 4VA |
| Material of Shell | ABS fireproof material |
| Weight | About 450 grams |
| Compressive Strength | AC2kVrms/min |
| Insulation Resistance | >100MΩ at DC500V |
| Dimensions | 120(L)× 110(W)× 75(H)mm |
| Installation Method | 35mm standard rail or fixed on the cabinet |
Dimension (Unit: mm)

Calibration Fine Tuning

PWR: Power indicator
SPAN: Calibration full scale potentiometer
ZERO: Zero potentiometer
Wiring


Tips: Active Power Transducers vs. Reactive Power Transducers
- Measurement Purpose: Active power transducers measure active power (W/kW) that performs actual work. Reactive power transducers measure reactive power (VAR/kVAR) that affects power quality but does no useful work.
- Application Focus: Choose active power transducers for energy monitoring, efficiency analysis, and load management. Use reactive power sensing for power factor correction and reactive power compensation.
- Load Type: Active power dominates in resistive loads (heaters, incandescent lamps). Reactive power is present in inductive/capacitive loads (motors, transformers, fluorescent lamps).
- Power Factor Impact: The higher the active power, the higher the efficiency. Excessive reactive power results in lower power factor, resulting in wasted energy and higher costs.