3 Phase AC Voltage Transducer 10V to 500V, Output 0-5V/4-20mA/0-20mA

$177.78
3 phase AC voltage transducer is a special voltage sensor for three-phase AC voltage measurement. Voltage transducer has a measuring range from AC 10V to 500V, supply voltage DC 12V/24V, output signal DC 0-5V/0-20mA/4-20mA. 3 phase voltage transducer is mainly used for power monitoring, power control and dispatching systems in petroleum, coal, metallurgy, railway and other industries.
SKU: ATO-VOS-3AC500
*
*
*
Free Shipping
Delivery date: 8-12 days

3 phase AC voltage transducer has measuring range of AC 10V/50V/100V/250V/300V to 500V.

Specification:

ModelATO-WB3U412U01ATO-WB3U414U01
Shipping weight1kg
Measuring range of input voltage *3 phase AC 0-10V ~ 0-500V
Short-time overload2 times of nominal input voltage, 1s in duration, interval time 10s, repeat 10 times
Linear measurement range0% ~ 120% measuring range
Frequency range25Hz ~ 1kHz
Input impedanceRi=2/3(Ux*1kΩ/V)
Output signal *DC 0-5VDC 0-20mA, 4-20mA
Power supply *DC 12V±10%, 24V±10%
Accuracy0.5%F.S.
Load capacity5mA6V
Response time≤300ms
Temperature drift250*10-6/℃350*10-6/℃
Static current≤8mAOutput 0-20mA: ≤12mA
Output 4-20mA: ≤35mA
Isolation featuresIsolation between input and output, output terminals provides power supply
Isolation voltageDC 2.5kV, 1min
Work temperature0~50℃
Storage temperature-25~+70℃
Protection class of housingIP20
Mean time between failures>50000h
Housing materialFire-retardant ABS
WiringTerminal connection
InstallationDIN rail (NS35/7.5, NS35/15, EN50022)

3 phase AC voltage transducer 10V to 500V dimensional drawing (unit: mm):
3 phase AC voltage transducer 10V to 500V dimension
3 phase AC voltage transducer output 0-5V wiring diagram:
3 phase AC voltage transducer output 0-5V wiring
3 phase AC voltage transducer output 0-20mA/4-20mA wiring diagram:
3 phase AC voltage transducer output 0-20mA/4-20mA wiring

Tips: Measuring requirements when using voltage sensors

To measure the voltage with a voltage sensor, it is generally required that the collected voltage signal is proportional to the measured voltage in amplitude, and the phase angles of the two are exactly the same or the difference is extremely small. In addition, there are the following basic requirements for the voltage sensor.

  1. The connection of the voltage sensor to the circuit under test should basically not affect the amplitude and waveform of the voltage under test.
  2. The voltage waveform obtained by the voltage sensor should be the same as the measured voltage waveform, and the voltage divider ratio should be independent of the measured voltage frequency and amplitude.
  3. The voltage divider ratio has nothing or basically nothing to do with atmospheric conditions (air pressure, temperature and humidity).
  4. The power consumed by the voltage sensor should not be large. Under certain cooling conditions, the temperature rise formed by the electrical energy dissipated by the voltage divider should not cause a change in the voltage divider ratio.
  5. The voltage sensor should not be interfered by the external electromagnetic field, and on the other hand, it should not produce strong electromagnetic interference from the external environment.
Product reviews
I want to buy your voltage sensor
5
Curtis
Avatar
9/21/2021 9:26 PM
I have come up with your product below:
Voltage Sensor
ATO-VOS-DC1000
Though, I have 2 questions:
1) I see there are several inputs for Voltage from 0V – 1000V. My first question is how can I select a range of fe150V?
In such case, what will the accuracy at low voltages fe 4V (I need accuracy of 2 decimals)?
Is there an option to switch between 2 ranges in one single sensor?
2) If I adjust the output range to 0-10V (this is my acceptable PLC input), what will be the output in case of reverse polarity connection? I really want to avoid a negative signal on my PLC input.
Was this review helpful? Yes No (0/0)
ATO Responded
1. Select required measuring range as you like from the pull down menu seen on the web site, and accuracy is: 0.2%F.S.
  No option is to switch between 2 ranges in one single sensor.
2. This is a DC voltage sensor, so the input voltage cannot reverse polarity connection, otherwise it may cause damage to the sensor.
Works as expected
5
Walter
Avatar
7/3/2025 4:08 PM
Great sensor, works as expected
Was this review helpful? Yes No (0/0)
Voltage measurement
4
Telis
Avatar
7/9/2025 8:04 PM
I have a three-phase AC voltage sensor model ATO-WB3U412U01. Can this sensor provide phase-to-ground voltage measurement when only one phase is connected? Or can it only measure phase-to-phase voltage?
Was this review helpful? Yes No (1/0)
ATO Responded
The ATO-WB3U412U01 three-phase AC voltage sensor you purchased can only measure phase-to-phase voltage, and cannot measure the voltage between the phase line and the ground.
Maximum AC voltage
5
Bercy
Avatar
1/13/2026 8:25 PM
We received a device with model number ATO-WB3U414U01_0.5. What is the maximum AC voltage of this device?
Was this review helpful? Yes No (0/0)
ATO Responded
The voltage sensor you purchased has a range of 0-300V. The input voltage to be detected should not exceed 300V, and the maximum should not exceed 360VAC.
Performance below zero temperatures
5
Kenny
Avatar
2/23/2026 11:41 PM
We purchased this 3-phase AC voltage transducer and want to know how it performs below zero temperatures. Will it break down or just experience a decrease in accuracy?
Was this review helpful? Yes No (0/0)
ATO Responded
Regarding the performance of this 3-phase AC voltage transducer below zero temperatures: Between 20°C and 0°C, it operates normally without damage. Between -25°C and -20°C, it is only suitable for power-off storage (it will not break down); powering it on will cause a significant decrease in accuracy, and prolonged use may damage internal components. Below -25°C: Exceeding the rated temperature range, regardless of whether it is powered on, can easily cause irreversible hardware damage and complete loss of measurement accuracy. We do not recommend using it in this environment.
Write your review
  • Only registered users can write reviews
*
*
  • Bad
  • Excellent
*
*
*
*

3 phase AC voltage transducer has measuring range of AC 10V/50V/100V/250V/300V to 500V.

Specification:

ModelATO-WB3U412U01ATO-WB3U414U01
Shipping weight1kg
Measuring range of input voltage *3 phase AC 0-10V ~ 0-500V
Short-time overload2 times of nominal input voltage, 1s in duration, interval time 10s, repeat 10 times
Linear measurement range0% ~ 120% measuring range
Frequency range25Hz ~ 1kHz
Input impedanceRi=2/3(Ux*1kΩ/V)
Output signal *DC 0-5VDC 0-20mA, 4-20mA
Power supply *DC 12V±10%, 24V±10%
Accuracy0.5%F.S.
Load capacity5mA6V
Response time≤300ms
Temperature drift250*10-6/℃350*10-6/℃
Static current≤8mAOutput 0-20mA: ≤12mA
Output 4-20mA: ≤35mA
Isolation featuresIsolation between input and output, output terminals provides power supply
Isolation voltageDC 2.5kV, 1min
Work temperature0~50℃
Storage temperature-25~+70℃
Protection class of housingIP20
Mean time between failures>50000h
Housing materialFire-retardant ABS
WiringTerminal connection
InstallationDIN rail (NS35/7.5, NS35/15, EN50022)

3 phase AC voltage transducer 10V to 500V dimensional drawing (unit: mm):
3 phase AC voltage transducer 10V to 500V dimension
3 phase AC voltage transducer output 0-5V wiring diagram:
3 phase AC voltage transducer output 0-5V wiring
3 phase AC voltage transducer output 0-20mA/4-20mA wiring diagram:
3 phase AC voltage transducer output 0-20mA/4-20mA wiring

Tips: Measuring requirements when using voltage sensors

To measure the voltage with a voltage sensor, it is generally required that the collected voltage signal is proportional to the measured voltage in amplitude, and the phase angles of the two are exactly the same or the difference is extremely small. In addition, there are the following basic requirements for the voltage sensor.

  1. The connection of the voltage sensor to the circuit under test should basically not affect the amplitude and waveform of the voltage under test.
  2. The voltage waveform obtained by the voltage sensor should be the same as the measured voltage waveform, and the voltage divider ratio should be independent of the measured voltage frequency and amplitude.
  3. The voltage divider ratio has nothing or basically nothing to do with atmospheric conditions (air pressure, temperature and humidity).
  4. The power consumed by the voltage sensor should not be large. Under certain cooling conditions, the temperature rise formed by the electrical energy dissipated by the voltage divider should not cause a change in the voltage divider ratio.
  5. The voltage sensor should not be interfered by the external electromagnetic field, and on the other hand, it should not produce strong electromagnetic interference from the external environment.
Product reviews
I want to buy your voltage sensor
5
Curtis
Avatar
9/21/2021 9:26 PM
I have come up with your product below:
Voltage Sensor
ATO-VOS-DC1000
Though, I have 2 questions:
1) I see there are several inputs for Voltage from 0V – 1000V. My first question is how can I select a range of fe150V?
In such case, what will the accuracy at low voltages fe 4V (I need accuracy of 2 decimals)?
Is there an option to switch between 2 ranges in one single sensor?
2) If I adjust the output range to 0-10V (this is my acceptable PLC input), what will be the output in case of reverse polarity connection? I really want to avoid a negative signal on my PLC input.
Was this review helpful? Yes No (0/0)
ATO Responded
1. Select required measuring range as you like from the pull down menu seen on the web site, and accuracy is: 0.2%F.S.
  No option is to switch between 2 ranges in one single sensor.
2. This is a DC voltage sensor, so the input voltage cannot reverse polarity connection, otherwise it may cause damage to the sensor.
Works as expected
5
Walter
Avatar
7/3/2025 4:08 PM
Great sensor, works as expected
Was this review helpful? Yes No (0/0)
Voltage measurement
4
Telis
Avatar
7/9/2025 8:04 PM
I have a three-phase AC voltage sensor model ATO-WB3U412U01. Can this sensor provide phase-to-ground voltage measurement when only one phase is connected? Or can it only measure phase-to-phase voltage?
Was this review helpful? Yes No (1/0)
ATO Responded
The ATO-WB3U412U01 three-phase AC voltage sensor you purchased can only measure phase-to-phase voltage, and cannot measure the voltage between the phase line and the ground.
Maximum AC voltage
5
Bercy
Avatar
1/13/2026 8:25 PM
We received a device with model number ATO-WB3U414U01_0.5. What is the maximum AC voltage of this device?
Was this review helpful? Yes No (0/0)
ATO Responded
The voltage sensor you purchased has a range of 0-300V. The input voltage to be detected should not exceed 300V, and the maximum should not exceed 360VAC.
Performance below zero temperatures
5
Kenny
Avatar
2/23/2026 11:41 PM
We purchased this 3-phase AC voltage transducer and want to know how it performs below zero temperatures. Will it break down or just experience a decrease in accuracy?
Was this review helpful? Yes No (0/0)
ATO Responded
Regarding the performance of this 3-phase AC voltage transducer below zero temperatures: Between 20°C and 0°C, it operates normally without damage. Between -25°C and -20°C, it is only suitable for power-off storage (it will not break down); powering it on will cause a significant decrease in accuracy, and prolonged use may damage internal components. Below -25°C: Exceeding the rated temperature range, regardless of whether it is powered on, can easily cause irreversible hardware damage and complete loss of measurement accuracy. We do not recommend using it in this environment.
Only registered users can write reviews
Customers who bought this item also bought

AC Current Sensor, AC 200A/400A/600A/800A

ATO-CUS-AC800
$88.25
AC current sensor adopts electromagnetic isolation principle, small size, light weight, low price, fast response, high accuracy, good stability, 35mm/45mm/55mm hole diameter, and screws fixed installation. AC current sensor is widely used for AC current measurement of various occasions, especially for sine-wave ac current with power frequency 50Hz.

3 Phase AC Current Transducer 0.5A/1A/2A/5A/10A/20A/50A to 80A

ATO-CUS-3AC80
$161.39
AC current transducer is a special current sensor for 3 phase AC current measurement. Three phase current transducer adopts epoxy resin pouring sealant to ensure the stability of components, with 0.5%FS accuracy, three output signals 4-20mA/0-20mA/0-5V/0-10V, power supply DC 5V/12V/24V, fixed installation. 3 phase AC current transducer is widely used for real-time monitoring of power grid AC current.

DC Current Sensor 1mA/1A/5A/10A/100A to 800A

ATO-CUS-DC800
$85.56
DC current sensor has best cost performance, fast response, high accuracy, good stability, small size, light weight, DIN rail installation, widely used for DC current measurement of various occasions.

Isolated DC Voltage Sensor 10mV to 1000V, Power Supply DC 12V/24V

ATO-VOS-DC1000
$141.96
DC voltage sensor uses modulation and demodulation technology to achieve input/output/power supply isolation. Isolated voltage transducer has measuring range from DC 10mV/50mV/75mV/5V/150V/300V/500V to 1000V, supply voltage DC 12V/24V, accuracy 0.2%FS, output signal 0-5V/0-10V/0-20mA/4-20mA and strong anti-interference capability. DC voltage sensor is widely used for voltage isolated measuring and control, such as electric power, remote monitoring, medical equipment, etc.

AC/DC Voltage Sensor 75mV to 500V, RMS 0-5V/0-10V/4-20mA/0-20mA Output

ATO-VOS-ACDC500
$161.27
Voltage sensor has voltage measuring range from AC/DC 75mV/50V/100V/250V/300V to 500V, supply voltage DC 12V/24V, output DC voltage/current or True RMS voltage/current signal 0-5V/0-10V/0-20mA/4-20mA and protection class IP20. AC/DC voltage sensor has two installation methods, DIN rail installation and M3 screw fixation.