Current transformer is one of important devices for power system and used to transform the voltage or current. Current radio 50:5A, 100:5A, 250:5A, to 400:5A. AC current transformer with rated frequency 50Hz or 60Hz, free shipping and good value for money.
Note: The installation method of current transformer can be fixed by busbar and fixed by the bottom plate, suitable for installation in any direction. The primary conductor can be busbar or cable.
Specification:
| Model | ATO-CT-3030I | |||
| Weight | 1kg | |||
| Current Ratio (A) | VA Secondary load/ Burden (VA) | Cross-core Turn Number | ||
| 0.2 | 0.5S | 0.2S | ||
| 30/A | 2.5 | 2.5 | 2.5 | 3 |
| 50/5 | 2.5 | 2.5 | 2.5 | 2 |
| 75/5 | 2.5 | 2.5 | 2.5 | 2 |
| 100/5 | 2.5 | 2.5 | 2.5 | 1 |
| 150/5 | 2.5 | 1.5 | 1.5 | 5 |
| 200/5 | 5 | 5 | 3.75 | 1 |
| 250/5 | 5 | 5 | 5 | 1 |
| 300/5 | 5 | 5 | 5 | 1 |
| 400/5 | 5 | 5 | 5 | 1 |
| Rated Frequency | 50/60Hz | |||
| Rated Test Voltage | 3kV AC (1min) | |||
| Rated Short-Time Thermal Current (ith) | 60 in | |||
| Rated Dynamic Current (idyn) | 2.5 lth | |||
| Rated Voltage (Um) | 0.66 kV AC | |||
| Continuous Overload (ld) | 1.2 in | |||
| Operating Temperature | -10℃~50℃ | |||
| Housing Self-Extinguishing Class | VO | |||
| Safety Factor | FS 5 | |||
| Secondary Current | 5A/ 1A | |||
| Bus Specification (mm)/Number | / | |||
Dimension (unit: mm)

| Model | Dimensions | Perforation size | Installation size | |||||
| W | H | D | a | e | φ | M | N | |
| ATO-CT-30I | 62 | 78 | 45 | 32 | 11 | 22 | 40 | 57.5 |
| ATO-CT-3030I | 85 | 102 | 50 | 32 | 11 | 28 | 57.5 | |
| ATO-CT-40I | 75 | 95 | 45 | 42 | 11 | 31 | 40 | 57.5 |
| ATO-CT-60I | 102 | 130 | 45 | 61.5 | 21 | 45 | 42 | 57.5 |
| ATO-CT-60II | 102 | 125 | 45 | 31 | 33 | / | 42 | 57.5 |
| ATO-CT-80I | 118 | 140 | 45 | 82 | 11 | 52 | 60 | 57.5 |
| ATO-CT-100II | 145 | 125 | 45 | 103 | 35 | / | 80 | 57.5 |
Tips: What causes the current transformer to burn out?
- Secondary open circuit of the current transformer produces high voltage to burn out the current transformer.
- Long-term use of the current transformer makes the insulation aging, local breakdown or discharge occurs and overvoltage is thereof produced, thus burning out the current transformer.
- Long-term overload operation makes the current transformer to give out heat, it is thereof burned out.
- The aluminum contact surface of current transformer’s primary connection is seriously oxidized, which results in large contact resistance. The contact resistance gives out heats and burns out the current transformer.
Product reviews
Can you proivde 8500A/5A current transformer?
Mikem
5/17/2021 9:41 PM
Can you proivde 8500A/5A current transformer?
Was this review helpful? (0/0)
Very delicate AC transformer
Vincent
4/12/2022 3:25 AM
I bought a 400/5A current transformer again, the price is cheap, it matches the description, it has been installed and used, and the quality is reliable.
Was this review helpful? (0/0)
Current transformer requirement
Kylia
1/4/2026 11:32 PM
We are looking for a current transformer with a primary current range of 63A to 100A and a secondary current of 5A. Does your company have a product with model number ATO-CT-3030I?
Was this review helpful? (0/0)
Only registered users can write reviews
Customers who bought this item also bought
Current Transformer, 10/5A, 20/5A, 40/5A to 75/5A
ATO-CT-30I
$85.93
Current transformer current ratio can select 10/5A, 25/5A, 50/5A and 75/5A, accuracy classes can choose 0.5s, 0.2, 0.2s, rated frequency 50 Hz/60Hz, low cost and manufacturer direct sale.