Affordable price 30 kVA static frequency converter, change 60 Hertz to 50 Hertz, boost 208V 240V to 400V/415V, output three phase or single phase, pure sine wave AC power source.
Specification:
| Model | HZ-50-3330 | |
| Capacity | 30 kVA | |
| Dimension | 900*800*1200 mm | |
| Weight | 330 kg | |
| Input | Voltage | 3 Phase 4 Wire: Wye Type 190/110, 200/115, 208/120, 220/128, 230/132, 240/139V ±10% (option *) |
| 3 Phase 4 Wire: Wye Type 380/220, 400/230, 415/240, 440/254, 460/265, 480/277V ± 10% (option *) | ||
| 3 Phase 4 Wire: Della Type 220, 230, 240, 380, 400, 415, 440V ± 10% (option *) | ||
| Frequency | 50 Hz, 60 Hz | |
| Output | Voltage, current | 110V Setting (Low grade): 0-150V (phase voltage), 0-260V (line voltage) 83.2A |
| 220V Setting (High grade): 0-300V (phase voltage), 0-520V (line voltage) 41.6A | ||
| Load stabilization Rate | ≤±1% | |
| Frequency | 50Hz, 60Hz up to 400Hz adjustable Note: -When the output is 400Hz, the load capacity can only reach 50% of the rated capacity. -When the output is ≤120Hz, the load capacity can reach 100% of the rated value. -You can just adjust converter output frequency in the range (40-400Hz) for 400Hz option. | |
| Frequency Stability | ≤±0.01% | |
| Harmonic Distortion | Pure Sine Wave ≤2% | |
| Frequency meter | 4 digit, digital frequency meter, resolution 0.1Hz/Step | |
| Voltmeter | 4 digit, digital voltage meter, resolution 0.1V | |
| Ammeter | 4 digit, digital ammeter, resolution 0.1A | |
| Watt meter | 4 digit, digital Watt meter, resolution 0.1W | |
| Protection | With overload, short circuit, over temperature | |
| Instantaneous power failure protection and alarm device | ||
| Working Environment | Temperature | 0 - 40 deg.℃ |
| Humidity | 0 - 90% (Non condensation) | |
| Warranty | 18 months | |
Tips: Why choose frequency converter?
Since the power source of various countries in the world are not uniform, the production of export products needs to simulate the electric grid conditions of different countries to test various export appliances. In the past, the generator was used for secondary frequency conversion, but the power consumption was large, the noise was large, and the stability was poor. The frequency converter is a kind of precision power supply that converts the mains into the required voltage and frequency through the power conversion circuit. It can convert 50Hz to 60Hz or 60Hz to 50Hz, output pure sine wave, and can provide standard voltage and frequency of various countries in the world, suitable for voltage and frequency testing of export products. More and more countries select frequency converter as a standard power supply.
The main motor will be run from a VFD, and the entire system should draw less than 5 KVA at 230v, 3 phase, 50hz.
It looks like the 10 KVA 400hz converter we got from you can also do 50 or 60 hz outputs. Would it still be capable of the full rated line amperage and voltage at these low frequencies?
The U & W leg are working properly but as you can see on the V-leg that it does not have adequate Hz and voltage. I have problems compressing my video to email to you. I will continue to work on compressing it and will forward once I am able.
Because the parts are being sent on regular international freight and are probably being bumped for priority freight.
We cannot get a definite date on when we will get the part and we need to get operational ASAP.
Can we disconnect the V-Phase to allow us continued functionality of the W
How to use and protect this one with 220V/50hz local supply power ?
I understand that there is hardware module/modules that needs to be exchanged to change the input voltage, correct?
Unfortunately, shipping the unit back to the factory for such a change is not an option due to the time and cost involved.
Would it be possible to order such modules, including sufficient documentation with instructions, enabling our technicians/electricians to make this adaption between our different missions?
I have no problem that any such field work would be completely under the users own responsibility and void any warranty that may exist for the unit.
Thanks for your continued support.
The incoming voltage is 420V when measured at the input terminal lugs. I am able to turn on the input breaker and press the power button. The output voltage measured is 211V phase and 122V line. When I switch the output breaker, I get an alarm and one phase drops to 0V while the other 2 phase maintain voltage.