Wholesale price air-cooled industrial water chiller with 8 ton large cooling capacity, equipped with 2 compressors and total power of 10 HP, finned type condenser, spiral type or tube-in-shell type evaporator for choice. The machine interface configures a full touch screen, which enables automatic control and accurate monitoring.
SKU: ATO-IWC-10HP
*
*
*
*
Ship to
*
*
Shipping Method
Name
Estimated Delivery
Price
No shipping options
Delivery date: 8-12 days

10 HP portable water chiller machine for sales, 8 ton refrigerating capacity, works in three-phase four wire 50Hz or 60Hz power supply, 240V/ 400V/ 480V AC voltage are optional. It is widely used in industrial injection molding machines, film-blowing machines, laser cutting, chemical and pharmaceutical fields, etc.

Features

  • Adopted high-quality compressors and pumps to ensure safe & quiet running, power saving and durable service life.
  • Employed microcomputer with easy operation which can control the temperature within 3℃ to 45℃ precisely.
  • Unique design for condenser and heat-dispersion unit results in excellent heat-exchange effect.
  • Equipped with electrical current overload protection, high & low-pressure switch, and electrical timer delay safety device. It will alarm to display faulty when any malfunction occurs.
  • Built-in stainless steel insulated water tank, durable and easy to clean.
  • Complete safety devices including power reverse phase, power short phase and anti-freeze protection.
  • Ultra low-temperature type of chiller can reach below -60℃.

Parameter

ModelATO-LC10A
Cooling Capacity8 ton
Number of Compressors2
Compressor Total Power10 HP
RefrigerantR22 / R407C (Optional)
Evaporator TypeSpiral type / Tube-in-shell type (Optional)
Condenser TypeFinned
Cooling TypeAir-cooled
Number of Fans2
Single Fan power0.25kW
Number of Cooling Water Inlet/Outlet1 group
Cooling Water Inlet/Outlet SizeDN40
Water Tank Capacity145L
Pump Power1 HP
Pump Flow200L/min
Pump Lifts13M
Power Supply3-phase 4-wire AC 208V/60Hz, 220V/60Hz, 240V/60Hz, 380V/50Hz, 400V/50Hz, 415V/50Hz, 480V/60Hz (Optional)
Control Voltage1-phase AC 220V (L+N)
Total Power8.8kW
Wires Specifications4x6mm2
Chilled Water Temperature Range5℃~35℃
Inlet/Outlet Water Temperature Difference3℃~8℃
Condensation Temperature≤ 35℃
CertificationCE
DimensionL*W*H=1500*730*1400mm
Net Weight / Gross Weight450kg / 500kg


Shipping Way of ATO Water Chiller

Just confirm the shipping way by email when place your order.

1. Ship by Air: The compressed refrigerant inside the chiller is a dangerous item with the possibility of explosion, so it needs to release the compressed refrigerant before transportation. (It means that water chiller without refrigerant when choosing this shipping way. After the machine arrives at your destination, you need to add refrigerant by local professionals, the process is as simple as adding refrigerant for ordinary air conditioners). Delivery time is about 15-30 days.

2. Ship by Sea: The transportation time is longer (about 40-55 days), and there is no need to add refrigerant after the equipment arrives at the destination.

Note:

1. The "cooling capacity" is tested based on the inlet and outlet water temperature of freezing is 12℃/7℃, and the inlet and outlet water temperature of cooling is 30℃/35℃.

2. Conversion of units: 1 ton cooling capacity=3024kcal/hr, 1kcal/hr=3.969BTU/hr, 1HP=0.735kW=2580kcal/hr

Evaporator Types

Water chiller evaporator types

Type 1: Water Tank with Coil

  • Integrated Design: The industrial water chiller features a built-in open-top water tank with an integrated coil, providing a compact and self-contained cooling solution.
  • Sealed Circulation: The water circuit operates in a sealed loop, ensuring stable performance and preventing contamination.
  • Direct Connection: The air-cooled water chiller supports direct connection to equipment requiring cooling, with no external tank needed.

Type 2: Shell and Tube

  • Tankless Configuration: This water chiller is designed without an internal water tank and relies on an external open water tank for operation.
  • Application: Specifically suitable for cooling external open water tanks, pools, or reservoirs in industrial and commercial applications.

Water Chiller Structure Diagram

water chiller structure diagram

①Compressor②High-pressure gauge③Condenser④Dry filter
⑤Expansion valve⑥Water supply⑦Evaporator⑧Low-pressure gauge
⑨Water tank⑩Drain⑪Refrigerated water⑫Pump


Tips: Can an industrial water chiller be cleaned with acid?

In normal applications, the chiller requires regular and scientific cleaning, which is also an indispensable part of maintenance. Mainly condensers, evaporators, various pipes, etc., especially the condensers and evaporators of water-cooled type chiller, must be regularly cleaned.

Pickling can be applied as a cleaning method. However, the degree of dilution of the acid solution and the type of acid solution need to be considered. Basically, almost all condensers can be cleaned using acid. In addition, it is necessary to consider whether the components of the water chiller to be cleaned are a certain part or the entire cycle operation system. These two aspects are completely different.

In case of cleaning the circulating operation system, it is necessary to ensure that the system is completely closed, and connect the cleaning pump, liquid distribution tank and relevant valves of the refrigerator. If it is cleaned separately, it is necessary to remove the condenser, and then add the diluted acid into it. It must be filled to achieve the corresponding cleaning effect. The reason why it is necessary to clean the chiller is that there are many parts in the chiller that will affect the normal operation of the whole water chiller.

How to Fill an Industrial Water Chiller with Refrigeran?

This video shows how to fill an industrial water chiller with refrigerant. The steps for filling a chiller with refrigerant are similar to those for filling an air conditioner with refrigerant, first drain the air and then fill the equipment with refrigerant.

Product reviews
Awesome
5
Drew
Avatar
3/15/2022 7:52 PM
This 8 ton water chiller has serviced our 100 watt laser very well. Setup was quick and easy, everything has worked smoothly. So far so good! I will order more.
Was this review helpful? Yes No (0/0)
So far so good
5
Octavio
Avatar
4/8/2022 12:06 AM
This water chiller hasn't given us any problems so far. Hopefully that will continue for several years. I like it. I am very pleased with its performance. I completely recommend this product.
Was this review helpful? Yes No (0/0)
I want pump curve for the system
5
Keran
Avatar
8/14/2023 12:10 AM
I bought this water chiller last week. That does not include the pump curve for the system, can you provide that so that I can confirm if it is acceptable for our needs?
Was this review helpful? Yes No (0/0)
ATO Responded
Unfortunately, we do not provide the pump curve for the system.
Chiller Maintenance
5
Ernasi
Avatar
7/1/2025 12:40 AM
Can you provide the highest and lowest pressures of this chiller? We need this information for maintenance.
Was this review helpful? Yes No (0/0)
ATO Responded
Please pay attention to the pressure gauge when the unit is running. The high pressure should be less than 20kgf/cm2 and the low pressure should be greater than 2.5kgf/cm2. A pressure lower than 2.5kgf/cm2 indicates that there may be a leak in the system, and a pressure higher than 20kgf/cm2 indicates that maintenance is required.
Write your review
  • Only registered users can write reviews
*
*
  • Bad
  • Excellent
*
*
*
*

10 HP portable water chiller machine for sales, 8 ton refrigerating capacity, works in three-phase four wire 50Hz or 60Hz power supply, 240V/ 400V/ 480V AC voltage are optional. It is widely used in industrial injection molding machines, film-blowing machines, laser cutting, chemical and pharmaceutical fields, etc.

Features

  • Adopted high-quality compressors and pumps to ensure safe & quiet running, power saving and durable service life.
  • Employed microcomputer with easy operation which can control the temperature within 3℃ to 45℃ precisely.
  • Unique design for condenser and heat-dispersion unit results in excellent heat-exchange effect.
  • Equipped with electrical current overload protection, high & low-pressure switch, and electrical timer delay safety device. It will alarm to display faulty when any malfunction occurs.
  • Built-in stainless steel insulated water tank, durable and easy to clean.
  • Complete safety devices including power reverse phase, power short phase and anti-freeze protection.
  • Ultra low-temperature type of chiller can reach below -60℃.

Parameter

ModelATO-LC10A
Cooling Capacity8 ton
Number of Compressors2
Compressor Total Power10 HP
RefrigerantR22 / R407C (Optional)
Evaporator TypeSpiral type / Tube-in-shell type (Optional)
Condenser TypeFinned
Cooling TypeAir-cooled
Number of Fans2
Single Fan power0.25kW
Number of Cooling Water Inlet/Outlet1 group
Cooling Water Inlet/Outlet SizeDN40
Water Tank Capacity145L
Pump Power1 HP
Pump Flow200L/min
Pump Lifts13M
Power Supply3-phase 4-wire AC 208V/60Hz, 220V/60Hz, 240V/60Hz, 380V/50Hz, 400V/50Hz, 415V/50Hz, 480V/60Hz (Optional)
Control Voltage1-phase AC 220V (L+N)
Total Power8.8kW
Wires Specifications4x6mm2
Chilled Water Temperature Range5℃~35℃
Inlet/Outlet Water Temperature Difference3℃~8℃
Condensation Temperature≤ 35℃
CertificationCE
DimensionL*W*H=1500*730*1400mm
Net Weight / Gross Weight450kg / 500kg


Shipping Way of ATO Water Chiller

Just confirm the shipping way by email when place your order.

1. Ship by Air: The compressed refrigerant inside the chiller is a dangerous item with the possibility of explosion, so it needs to release the compressed refrigerant before transportation. (It means that water chiller without refrigerant when choosing this shipping way. After the machine arrives at your destination, you need to add refrigerant by local professionals, the process is as simple as adding refrigerant for ordinary air conditioners). Delivery time is about 15-30 days.

2. Ship by Sea: The transportation time is longer (about 40-55 days), and there is no need to add refrigerant after the equipment arrives at the destination.

Note:

1. The "cooling capacity" is tested based on the inlet and outlet water temperature of freezing is 12℃/7℃, and the inlet and outlet water temperature of cooling is 30℃/35℃.

2. Conversion of units: 1 ton cooling capacity=3024kcal/hr, 1kcal/hr=3.969BTU/hr, 1HP=0.735kW=2580kcal/hr

Evaporator Types

Water chiller evaporator types

Type 1: Water Tank with Coil

  • Integrated Design: The industrial water chiller features a built-in open-top water tank with an integrated coil, providing a compact and self-contained cooling solution.
  • Sealed Circulation: The water circuit operates in a sealed loop, ensuring stable performance and preventing contamination.
  • Direct Connection: The air-cooled water chiller supports direct connection to equipment requiring cooling, with no external tank needed.

Type 2: Shell and Tube

  • Tankless Configuration: This water chiller is designed without an internal water tank and relies on an external open water tank for operation.
  • Application: Specifically suitable for cooling external open water tanks, pools, or reservoirs in industrial and commercial applications.

Water Chiller Structure Diagram

water chiller structure diagram

①Compressor②High-pressure gauge③Condenser④Dry filter
⑤Expansion valve⑥Water supply⑦Evaporator⑧Low-pressure gauge
⑨Water tank⑩Drain⑪Refrigerated water⑫Pump


Tips: Can an industrial water chiller be cleaned with acid?

In normal applications, the chiller requires regular and scientific cleaning, which is also an indispensable part of maintenance. Mainly condensers, evaporators, various pipes, etc., especially the condensers and evaporators of water-cooled type chiller, must be regularly cleaned.

Pickling can be applied as a cleaning method. However, the degree of dilution of the acid solution and the type of acid solution need to be considered. Basically, almost all condensers can be cleaned using acid. In addition, it is necessary to consider whether the components of the water chiller to be cleaned are a certain part or the entire cycle operation system. These two aspects are completely different.

In case of cleaning the circulating operation system, it is necessary to ensure that the system is completely closed, and connect the cleaning pump, liquid distribution tank and relevant valves of the refrigerator. If it is cleaned separately, it is necessary to remove the condenser, and then add the diluted acid into it. It must be filled to achieve the corresponding cleaning effect. The reason why it is necessary to clean the chiller is that there are many parts in the chiller that will affect the normal operation of the whole water chiller.

Product reviews
Awesome
5
Drew
Avatar
3/15/2022 7:52 PM
This 8 ton water chiller has serviced our 100 watt laser very well. Setup was quick and easy, everything has worked smoothly. So far so good! I will order more.
Was this review helpful? Yes No (0/0)
So far so good
5
Octavio
Avatar
4/8/2022 12:06 AM
This water chiller hasn't given us any problems so far. Hopefully that will continue for several years. I like it. I am very pleased with its performance. I completely recommend this product.
Was this review helpful? Yes No (0/0)
I want pump curve for the system
5
Keran
Avatar
8/14/2023 12:10 AM
I bought this water chiller last week. That does not include the pump curve for the system, can you provide that so that I can confirm if it is acceptable for our needs?
Was this review helpful? Yes No (0/0)
ATO Responded
Unfortunately, we do not provide the pump curve for the system.
Chiller Maintenance
5
Ernasi
Avatar
7/1/2025 12:40 AM
Can you provide the highest and lowest pressures of this chiller? We need this information for maintenance.
Was this review helpful? Yes No (0/0)
ATO Responded
Please pay attention to the pressure gauge when the unit is running. The high pressure should be less than 20kgf/cm2 and the low pressure should be greater than 2.5kgf/cm2. A pressure lower than 2.5kgf/cm2 indicates that there may be a leak in the system, and a pressure higher than 20kgf/cm2 indicates that maintenance is required.
Only registered users can write reviews