Lightweight water flow switch with digital display can monitor data in real time. It is designed with water sensor, PNP or NPN signal output for transmitting data to the mainboard.
Specification
| Model | ATO-NPF3W70403 | |
| Port Size Rc (PT) | 3/8 inch | |
| Applicable Fluid | Water, Ethylene glycol aqueous solution (with viscosity of 3 MPa·s [3 cP] or less) | |
| Detection Method | Karman vortex | |
| Rated Flow Range | 0.5~4L/min | |
| Display Flow Range | 0.35~5.50L/min | |
| Set Flow Range | 0.35~5.50L/min | |
| Smallest Settable Increment | 0.01L/min | |
| Conversion of Accumulated Pulse | 0.05L/pulse | |
| Fluid Temperature | 0 to 90°C (No freezing or condensation) | |
| Display Unit | Instantaneous flow: L/min, Accumulated Flow: L | |
| Accuracy | Display value: ±3% F.S. Analog output: ±3% F.S. | |
| Repeatability | ±2% F.S | |
| Temperature Characteristics | ±5% F.S. (25°C standard) | |
| Operating Pressure Range | 0~1MPa | |
| Proof Pressure | 45kPa or less at the maximum flow | |
| Accumulated Flow Range | 99999999.9L | |
| By 0.1L | ||
| Switch Output | / | NPN or PNP |
| Max. Load Current | 80mA | |
| Max. Applied Voltage | DC28V | |
| Internal Voltage Drop | NPN: 1 V or less (at load current of 80 mA) PNP: 1.5 V or less (at load current of 80 mA) | |
| Response Time | 0.5s/ 1s/ 2s | |
| Output Protection | Short-circuit protection | |
| Analog Output | Voltage Output | Voltage output: 1 to 5 V Output impedance: 1 kΩ |
| Current Output | Output current: 4 to 20 mA Max. load impedance: 300 Ω for 12 VDC, 600 Ω for 24 VDC | |
| Response Time | 0.5s/ 1s/ 2s (linked with the switch output) | |
| Hysteresis | Variable | |
| External Input | Voltage free input: 0.4 V or less (Reed or Solid state), input for 30ms or longer | |
| Display Method | 2-screen display (Main screen: 4-digit, 7-segment, 2-color, Red/Green Sub screen: 6-digit, 11-segment, White) Display values updated 5 times per second | |
| Indicator Light | Output 1, Output 2: Orange | |
| Power Supply Voltage | DC12~24V±10% | |
| Current Consumption | Below 50mA | |
| Environment | Enclosure | IP65 |
| Operating Temperature Range | 0 to 50°C (No freezing or condensation) | |
| Operating Humidity Range | Operation, storage: 35 to 85% R.H. (No condensation) | |
| Withstand Voltage | 1000 VAC for 1 minute between terminals and housing | |
| Insulation Resistance | 50 MΩ or more (500 VDC measured via megohmmeter) between terminals and housing | |
| Standards and Regulations | CE, UL(CSA), RoHS | |
| Wetted Parts Material | PPS. SUS304. FKM. SCS13, Non-grease | |
| Weight | 1kg | |
Flow Rate Diagram
Voltage Output: A: 1V, B: 1.5V, C: 5V
Current Output: A: 4mA, B: 6mA, C: 20mA

Pin Number & Wire Color

| Pin Number | Content | Wire Color |
| 1 | DC (+) | Brown |
| 2 | OUT2 | White |
| 3 | DC (-) | Blue |
| 4 | OUT1 | Black |
Body Dimensions (Unit: mm)

| Basic Dimensions | ||||||||||||
| A | AA | B | D | E | F | G | H | J | K | L | N | P |
| 70 | 50 | 30 | 60 | 40.6 | 15.2 | 24 | 14 | 35 | 26 | 18 | 13.6 | φ2.7 deep 14 |
| Bracket Dimensions | |||||||
| S | T | U | V | W | WX | Y | Z |
| 24 | 22 | 32 | 40 | 50 | 4.5 | 5 | 1.5 |
M8 Lead Wire Dimensions (Unit: mm)

Details

Tips for using a water flow switch
- The ambient temperature is not lower than 0°C. Do not knock on the housing and keep away from magnetic objects.
- The output of the signal is a switch quantity, so the connection method of the control object must also be a switch control.
- The power of the controlled object shall not be greater than the signal load capacity.
- The water flow switch is a water medium control device and cannot be used for other medium control.