4 pole mini circuit breaker (MCB) with a rated current of 10 amp is ideal for use in low voltage distribution systems. This miniature circuit breaker features a short circuit breaking capacity of 6 kA at 230/400V AC, ensuring that the breaker can quickly and effectively interrupt high fault currents, preventing potential fire hazards, equipment damage, and system failures.
4 Pole MCB Breaker Information
- Rated Current: 10 amp
- Rated Voltage: 230/400V AC, 50Hz
- Number of poles: 4 pole
- 6 kA rated short-circuit breaking capacity
- Compliant with IEC standard
- C curve trip characteristic
- With overload protection and short circuit protection function
Technical Data
| Model | ATO-NB8-634PC10 | |
| Rated Current | 10A | |
| Rated Voltage | 230/400V | |
| Frequency | 50Hz | |
| Number of Poles | 4P | |
| Mechanical Life | 20000 Times | |
| Electrical Life | 10000 Times | |
| Rated Short-Circuit Breaking Capacity | 6000A | |
| Operating Short-Circuit Breaking Capacity | 6000A | |
| Rated Impulse Withstand Voltage (1.2/50) | 6kV | |
| Dielectric Test Voltage | 2000V (50Hz, 1 min) | |
| Heat & Humidity Resistance | 28 Cycles | |
| Vibration Resistance | No Obvious Vibration and Impact | |
| Terminal Block | Terminal Block Type | Pillar Terminal Block |
| Min. Terminal Size Acceptability | 1mm2 | |
| Max. Terminal Size Acceptability | 25mm2 | |
| Standard Connection Torque | 2 N.m | |
| Max. Tolerable Torque | 2.5 N.m | |
| Wire Insertion Depth | 13mm | |
| Reference Temperature | 30℃ | |
| Operating Temperature | -35℃~+70℃ | |
| Storage Temperature | 35℃~+85℃ | |
| Applicable Altitude | 2000m | |
| Tripping Mode | Thermal Magnetic Trip | |
| Electromagnetic Tripping Type | Type C (5In-10In) | |
| Shell Flame Retardant Grade | V0 | |
| Wire Entry Method | Both Upper and Lower | |
| Installation Method | TH35-7.5 Standard Rail | |
| Protection Level | Direct Installation | IP20B |
| Installed in the Distribution Box | IP40B | |
4 Pole MCB Breaker Dimensions (Unit: mm)

Details

Tips: Common faults and solutions of miniature circuit breaker
Miniature Circuit Breakers (MCBs) are commonly used for protecting electrical circuits. Here are some common faults and their solutions:
Tripping without Load
- Cause: Mini circuit breaker may be faulty or worn out, or it could be due to an internal fault like insulation damage.
- Solution: Replace the MCB with a new one. Ensure no underlying circuit faults are causing the trip.
Frequent Tripping
- Cause: Overloading, short circuits, or earth faults.
- Solution: Check for overloaded circuits, and verify wiring for short circuits or grounding issues.
MCB Doesn't Trip on Overload
- Cause: The MCB's thermal element could be defective.
- Solution: Replace the faulty MCB.
Physical Damage
- Cause: External impact or deterioration over time.
- Solution: Replace the damaged MCB to prevent safety risks.
Failure to Reset
- Cause: Mechanical failure or internal fault.
- Solution: Inspect the micro circuit breaker and replace it if necessary.
Product reviews
Nice 10 amp 4 pole Miniature Circuit Breaker.
Oscar
4/20/2022 3:16 AM
I purchased this miniature circuit breaker as an additional protection and as a quick disconnect for my solar panels. It was easy to install and just snap it into place on the DIN rail. It is really nice, high quality MCB breaker that deserves 5 stars.
Was this review helpful? (0/0)
Very sturdy build.
Janette
10/28/2022 2:26 AM
This 4 pole miniature circuit breaker is worth the purchase. I used this for a generator to replace an older breaker. It works great and provides power on and off. You will be happy to invest in it. It makes a clean and well-designed DIN rail.
Was this review helpful? (0/0)
Very pleased with this purchase.
Marco
10/30/2022 7:44 PM
This 4 pole MCB I bought was used for a solar panel interrupter between panels and controller in an RV. Worked great. I am very pleased with this purchase and I will recommend this miniature circuit breaker to my friends and neighbors.
Was this review helpful? (0/0)
Only registered users can write reviews