10 kVA AC power frequency converter, three phase input, 1-phase or 3-phase output, change 60Hz to 50Hz for household appliances, 400Hz for military facilities, also convert 220 Volt to 380V/400V in one step.This type of frequency converter usually uses three-phase input and output, which can provide more stable voltage and greater power. It can also provide functions such as starting, braking and reversing of the motor to meet the power needs of more equipment.
Specification:
| Model | HZ-50-3310 | |
| Capacity | 10 kVA | |
| Dimension | 770 (D)*580 (W)*1140 (H) mm | |
| Weight | 150 kg | |
| Input | Voltage | 3 Phase 4 Wire: Wye Type 190/110, 200/115, 208/120, 220/128, 230/132, 240/139V ±10% (option *) |
| 3 Phase 4 Wire: Wye Type 380/220, 400/230, 415/240, 440/254, 460/265, 480/277V ± 10% (option *) | ||
| 3 Phase 4 Wire: Della Type 220, 230, 240, 380, 400, 415, 440V ± 10% (option *) | ||
| Frequency | 50 Hz, 60 Hz | |
| Output | Voltage, current | 110V Setting (Low grade): 0-150V (phase voltage), 0-260V (line voltage) 27.6A |
| 220V Setting (High grade): 0-300V (phase voltage), 0-520V (line voltage) 13.8A | ||
| Load stabilization Rate | ≤±1% | |
| Frequency | 50Hz, 60Hz up to 400Hz adjustable Note: -When the output is 400Hz, the load capacity can only reach 50% of the rated capacity. -When the output is ≤120Hz, the load capacity can reach 100% of the rated value. -You can just adjust converter output frequency in the range (40-400Hz) for 400Hz option. | |
| Frequency Stability | ≤±0.01% | |
| Harmonic Distortion | Pure Sine Wave ≤2% | |
| Frequency meter | 4 digit, digital frequency meter, resolution 0.1Hz/Step | |
| Voltmeter | 4 digit, digital voltage meter, resolution 0.1V | |
| Ammeter | 4 digit, digital ammeter, resolution 0.1A | |
| Watt meter | 4 digit, digital Watt meter, resolution 0.1W | |
| Protection | With overload, short circuit, over temperature | |
| Instantaneous power failure protection and alarm device | ||
| Working Environment | Temperature | 0 - 40 deg.℃ |
| Humidity | 0 - 90% (Non condensation) | |
| Warranty | 18 months | |
Tips: Can a motor with frequency of 60 Hz be connected to a 50 Hz power supply?
When the power supply voltage is constant, the power supply frequency is low, which is unfavorable for the operation of the motor. First, the increase in the magnetic flux density of the motor causes the core flux to saturate. At this time, the excitation current of the magnetic flux increases, so the increase of the total current of the stator of the motor increases, and the iron loss of the motor increases. The motor efficiency is reduced, the heat generation is increased, and the temperature rise is increased. According to the formula of the rotation speed n1=60f/p, n1 decreases, and the rotor rotation speed also decreases, so that the air volume is reduced, the heat dissipation is poor, and the motor temperature rises.
In order to use a 60 Hz motor for a 50 Hz power supply and not to generate heat, a method of lowering the power supply voltage can be used. Take a 380 volt motor as an example. In order to make the motor not overcurrent, it is necessary to maintain the magnetic flux density unchanged. Under the 50 Hertz power supply, the voltage at which the magnetic flux density is constant is (50/60) X380 = 317 volts. That is to say, as long as the power supply voltage drops to 317 volts, 60 Hz, the 380v motor will not generate heat on the 50Hz, 380v power supply. But pay attention to the following two issues. First, the motor speed will be reduced by about 17%. Second, since the voltage is 83% of the rated voltage, the power used after the step-down is only 83% of the original motor power.
In this case, ATO recommends using frequency converter as a standard power supply. AC power supply can step-up & step-down frequency and voltage, output pure sine wave, convert fixed frequency to the required frequency and voltage.
Input 1 phase, 240 VAC, 50 hz
To output: 1 phase, 240 VAC, 60 hz
This is for a pilot plant that was built in the US but is using Isreali power. Pumps and other motors for the unit are on VFDs. Our Inrush current is 70A. Looks like we need a HZ-50-1120? Is that correct?
we are manufacturing a machine compatible with European voltages (230/400VAC 50Hz).
This machine must also be able to be powered from an airport (115/200VAC 400Hz) as well as with USA voltage (120/210VAC 60Hz).
Can you confirm that it is possible to have 115/200VAC 400Hz three phase input and 230/400VAC 50Hz output?
Is the input voltage/frequency adjustable to 120/210VAC 60Hz or do I need to order another one with these specifications?
Thank you in advance for your reply.
Translated with www.DeepL.com/Translator (free version)
On page 12 there is a note stating that the input/output cable diameter should be doubled if over 20 meters. What is the reasoning behind this?
Is it for voltage drop? Is that the total length from the source panel?
Or does that get “reset” if there was a disconnect before the converter?
Also, are there any torque specifications on the input/output terminals?
The time has come for calibration and our end-user wants to ensure the unit is calibrated before using it for qualification tests.
Thanks.