The wall-mounted/embedded micro differential pressure transmitter is suitable for positive pressure, negative pressure or differential pressure gas pressure measurement of various ventilation and air-conditioning systems and equipment, with relay switch control and sound and light alarm. Both wall-mounted and embedded installation are possible. In addition, we can also provide customized products that meet the application needs of customers. If needed, please feel free to contact us.
Features
- Micro differential pressure transmitter has the default configuration where the low-pressure side is connected to the front panel and the high-pressure side to the side panel. For other requirements, please contact us.
- It has a built-in buzzer that provides both audible and visual alarms, with the ability to set the alarm pressure range on-site.
- The micro differential pressure transmitter uses imported components, offering low temperature drift and high stability to ensure long-term, reliable operation.
- The transmitter supports both wall-mounted and embedded installations, meeting the needs of various on-site applications.
- Its housing is made of flame-retardant ABS material, offering excellent impact resistance, heat resistance, and other outstanding properties.
Specification
| Model | ATO-CCY81 |
| Measuring medium | air and neutral gas (compatible with contact material and humidity <90RH%, no condensation) |
| Measuring range | 0~10kPa (optional, please contact us if other ranges are required) |
| Accuracy | 0.5%FS or 0.25%FS (range ≥1kPa) |
| 1%FS or 0.5%FS (range <1kPa) | |
| Pressure type | differential pressure |
| Output signal | RS485 |
| Alarm output | relay output *2 (contact capacity 220VAC, 3A) |
| Power supply voltage | 15~28VDC |
| Temperature compensation | -10~60℃ |
| Medium temperature | -10~60℃ |
| Connection time | 400ms |
| Response frequency | ≤5Hz |
| Stability performance | ±0.3%FS/year (range ≥1kPa) |
| ±0.5%FS/year (range ≤1kPa) | |
| Temperature drift | ±0.03%FS/℃ (within temperature compensation range) |
| Durability | 1x106 times (number of cycles from lower limit to upper limit of range) |
| Overall weight | about 365g |
| Protection level | IP65 |
| Resolution | 1/2000 |
| Maximum power | ≤0.015Us (W) |
| Insulation resistance | ≥100MΩ, 500VDC |
| Insulation strength | 500VAC |
| Environmental temperature | -40~85℃ |
| Environmental humidity | 0%~95%RH (no condensation and no condensation) |
| Certification | CE, ISO 9001, SGS |
Dimension (mm)

Wiring Instructions
| Type | Color | Description |
| Four-core signal line | red | Power+ |
yellow | 485A | |
blue | Power- | |
white | 485B | |
| Six-core control line | red | Normally open contact N/O |
black | Common COM | |
white | Normally closed contact NC | |
brown | Normally open contact N/O | |
green | Common COM | |
yellow | Normally closed contact NC |
Tips: Applications of micro differential pressure transmitter
- Industrial equipment: Used for differential pressure monitoring in various industrial equipment, such as compressors, pumps, filters, etc., ensuring optimal performance and maintenance of the equipment.
- Environmental monitoring: Applied for monitoring differential pressure in indoor and outdoor environments, including commercial buildings, residential buildings, weather monitoring, smart homes, hospital rooms, clean rooms, and more, to help maintain air quality and suitable environmental conditions.
- Pharmaceutical and biotechnology: Widely used in the pharmaceutical industry, life sciences, and biotechnology processes, including applications like pharmaceutical water, cleanroom control, disinfection and drying processes, disinfectant water, and more, ensuring product quality and the safety of the production environment.
- Cleanrooms and laboratories: Used for differential pressure monitoring in cleanrooms and laboratories to ensure proper airflow and cleanliness levels meet industry standards, safeguarding the accuracy and safety of experiments and production processes.
Only registered users can write reviews