4 pole AC contactor relay, 65amps, 24V/110V/220V coil voltage for selection, 4P (4NO) or 4P (2NO+2NC) contact form. As a bypass contactor, it is widely used for long-distance connecting and breaking circuit.
Specifications
| Model | ATO-CJX2-65 | |||
| Rated Operational Current (AC-3) | 380V | 65A | ||
| 660V | 42A | |||
| Conventional Heating Current | 80A | |||
| Rated Insulation Voltage | 690V | |||
| Power of Controllable 3-phase Squirrel-cage Motor (AC-3) | 220V | 18.5kW | ||
| 380V | 30kW | |||
| 660V | 37kW | |||
| Operational Frequency (AC-3) | Electric Life | 600 times/h | ||
| Mechanical Life | 3600 times/h | |||
| Service Life | Electric Life (104 times) | 60 | ||
| Mechanical Life (104 times) | 800 | |||
| Matching Fusing Model | RT16-80 | |||
| Average Power Consumption (20℃) @ 50Hz | Pick-up | 230VA | ||
| Holding | 32VA | |||
| Unit weight(kg) | 4P (4N/O) | 1.32 | ||
| 4P (2N/O+2N/C) | 1.37 | |||
| Ambient Temperature | -5℃~+40℃ | |||
| Altittude | ≤2000m | |||
| Rail Size | 75mm | |||
| Class of Pollution | Class 3 | |||
| Installation Category | Ⅲ | |||
Dimensions (unit: mm)
4P (4NO) AC contactor

4P (2NO+2NC) AC contactor

Tips: Coil overheating or burning, how to solve?
Possible Causes:
- The power supply voltage is too high or too low.
- Line technical parameters (such as rated voltage, frequency, load factor and applicable working system, etc.) do not match the actual use.
- Operating frequency is too high.
- Insulation damage due to poor coil manufacturing or mechanical damage.
- The moving part is stuck.
- The AC core is uneven or the magnetic air gap is too large.
- AC contactor derives the double coil of DC operation, because the normally closed interlocking contact welding does not release, and the coil is overheated.
Processing method:
- Adjust the power supply voltage.
- Exchange coils or contactors.
- Select other suitable contactors.
- Replace the coil to remove the obstacle that causes mechanical damage to the coil.
- Specially designed coils.
- Eliminate jamming.
- Clear the pole face or change the core.
- Adjust the interlocking contact parameters and replace the burnt coil.
Product reviews
Very practical product
Thomas
9/26/2018 9:31 PM
I purchased this contactor to replace the factory-installed contactor in my AC condensing unit. This part was a perfect replacement. The device arrives one week after payment in an undamaged cardboard box. My initial impression of the part was that it was very solid, of a good build-quality but so was the existing part that it was replacing. The connectors on this contactor were better than the original that I was replacing.
Was this review helpful? (0/0)
Only registered users can write reviews
Customers who bought this item also bought
25 amp 2/4 pole Lighting Contactor, 24V/110V/220V Coil
ATO-LCON-25
$66.58
2 pole & 4 pole Lighting contactors are relay switches, offer 25 amp, 100,000 cycles, optional auxiliary contacts and 12V/24V DC, 220V/110V AC coil voltage. Low noise and long life, operate at a safer load. AC contactor price is low. Magnetic contactor used to control lighting systems, supplies for home, large-scale industrial and commercial.