150 kVA 3 phase 220V 60 Hz to 400V, 380V 50 Hz static frequency converter, adjustable output Hertz (40.0 Hz - 400 Hz) and Volt (0 - 520V), convert fixed power supply to variable-frequency and variable-voltage.
Specification:
| Model | HZ-50-33150 | |
| Capacity | 150 kVA | |
| Dimension | 1500*860*1430 mm | |
| Weight | 800 kg | |
| Input | Voltage | 3 Phase 4 Wire: Wye Type 190/110, 200/115, 208/120, 220/128, 230/132, 240/139V ±10% (option *) |
| 3 Phase 4 Wire: Wye Type 380/220, 400/230, 415/240, 440/254, 460/265, 480/277V ± 10% (option *) | ||
| 3 Phase 4 Wire: Della Type 220, 230, 240, 380, 400, 415, 440V ± 10% (option *) | ||
| Frequency | 50 Hz, 60 Hz | |
| Output | Voltage, current | 110V Setting (Low grade): 0-150V (phase voltage), 0-260V (line voltage) 418A |
| 220V Setting (High grade): 0-300V (phase voltage), 0-520V (line voltage) 209A | ||
| Load stabilization Rate | ≤±1% | |
| Frequency | 50Hz, 60Hz up to 400Hz adjustable Note: -When the output is 400Hz, the load capacity can only reach 50% of the rated capacity. -When the output is ≤120Hz, the load capacity can reach 100% of the rated value. -You can just adjust converter output frequency in the range (40-400Hz) for 400Hz option. | |
| Frequency Stability | ≤±0.01% | |
| Harmonic Distortion | Pure Sine Wave ≤2% | |
| Frequency meter | 4 digit, digital frequency meter, resolution 0.1Hz/Step | |
| Voltmeter | 4 digit, digital voltage meter, resolution 0.1V | |
| Ammeter | 4 digit, digital ammeter, resolution 0.1A | |
| Watt meter | 4 digit, digital Watt meter, resolution 0.1W | |
| Protection | With overload, short circuit, over temperature | |
| Instantaneous power failure protection and alarm device | ||
| Working Environment | Temperature | 0 - 40 deg.℃ |
| Humidity | 0 - 90% (Non condensation) | |
| Warranty | 18 months | |
Product reviews
Failure analysis of 150kVA frequency converter
Thien
4/12/2021 9:43 PM
What will happen to the 150kVA frequency converter if it got sudden high inrush/surge current?
Was this review helpful? (1/0)
I want a frequency converter that meets our requirements
Nycgal
8/31/2021 12:15 AM
We need your brief specs for GoHz model HZ-50-1310 frequency converter with 1ph, 230V input, and 3-phase, 115V, 400Hz output?
Was this review helpful? (1/0)
I am interested in your frequency converter
Smiel
9/23/2021 7:05 PM
20kVA 3-Phase 380v 50Hz/220v 60Hz Frequency Converter
1) From your description I found that it has 3-phase 400V (3x230V)/50Hz input and 3-phase 220V(3x120V)/60Hz output. So on the output there are L1, L2, L3 (3x120V) and N available? Please confirm..
2) Do you have any office sales in Europe? What is the cost of delivery to Poland?
1) From your description I found that it has 3-phase 400V (3x230V)/50Hz input and 3-phase 220V(3x120V)/60Hz output. So on the output there are L1, L2, L3 (3x120V) and N available? Please confirm..
2) Do you have any office sales in Europe? What is the cost of delivery to Poland?
Was this review helpful? (0/0)
Frequency converter performance and use
Gotta
9/26/2021 7:10 PM
Hi, I have a site in Australia. We build air conditioning units for other countries and want to test the units. Looking for a converter that can convert 240v 50Hz to 120v 60Hz but also gave a variant on the 120v side, so the voltage can be varied. Is this something you could assist with?
Was this review helpful? (0/0)
Which frequency converter would you recommend to us?
Fredrik
10/11/2021 8:16 PM
We build boats and ship them to Europe regularly and they need to test the systems on the boats. We need to go from 120V 60Hz to 240V 50Hz. Currently they are using a generator to obtain the 50Hz, but it has been unreliable at best. They estimate the range to be between 30-50 Amps, possibly less. What do you recommend?
Was this review helpful? (0/0)
I need a frequency converter. Do you have any recommendations?
Denali
10/20/2021 8:11 PM
I need a frequency converter with:
Input: 400V, 50hz, three phase.
Output: 220V/110V 60Hz. What do you recommend?
Input: 400V, 50hz, three phase.
Output: 220V/110V 60Hz. What do you recommend?
Was this review helpful? (0/0)
We need the following frequency converter specs
Lhaas
1/11/2022 6:17 PM
We need the following converter specs: frequency converter, 400V/3phase/50Hz to 230v/3phase/60Hz and the capacity must be 40 kW and 100 Amps. What do you recommend?
Was this review helpful? (0/0)
Can you reproduce the documentation for this frequency converter?
berg
6/13/2023 2:04 AM
I hope you have been well. I am reaching out because we are starting to use the equipment from this order in short order after some unforeseen delays.
Unfortunately, during the delay the manuals/documents and CE declaration of conformity seem to have been misplaced.
Is there any way you could reproduce the documentation for this unit for us? I would really appreciate it.
Thank you very much.
Unfortunately, during the delay the manuals/documents and CE declaration of conformity seem to have been misplaced.
Is there any way you could reproduce the documentation for this unit for us? I would really appreciate it.
Thank you very much.
Was this review helpful? (0/0)
High efficiency converter
Phillip
5/7/2024 3:17 AM
The company recently purchased a number of converters, management took this purchase quite seriously and asked a couple questions. The first was whether there were any lower voltage range converters available? For example: One rated 0-150V per phase instead of 0-300V. Also, would this converter be able to help couple the converter with a power conditioner, or use a harmonic filter after the converter?
Was this review helpful? (0/0)
Only registered users can write reviews